SmartPAC 2 with WPC 2000 Integration User Manual
4-40
Initialization Mode
AUXILIARY OUTPUT 1 RESPONSE TO INTERRUPTED STROKE
If you have wired Auxiliary Output 1 (see page 2-35), switch 8 also controls how this output
responds to an Interrupted Stroke condition, as shown in Table 4-12.
When switch 8 is set to OPEN, its default setting, Aux. Output 1 turns “off” during an
Interrupted Stroke and whenever a fault occurs, an E-stop string opens, or a light curtain is
broken with the press running. When switch 8 is set to CLOSED, the Auxiliary Output stays
“on” during an Interrupted Stroke when no fault condition or E-stop occurs but turns “off”
whenever there is a fault, an open E-stop string, or a light curtain interruption.
* An Interrupted Stroke does not occur in Inch mode if the operator holds the palm switches
throughout the stroke. An Interrupted Stroke occurs in Inch only when the operator releases his
hands from the palm switches before the stroke is completed.
Making Operator Mode Settings
The DUAL OPERATORS, AUTOMATIC MODE, and TWO HAND ONLY items allow you
to make settings that control operator interaction with the WPC 2000. To set one of these
items, do the following:
1.
On the Press Control Option Switch Menu, move the highlight bar to the operator mode
item you want.
2.
Press ENTER until the setting you want is displayed.
3.
Repeat steps 1 and 2 for each operator mode you want to set.
NON-SAFETY OUTPUTS USED FOR SAFETY FUNCTIONS
Use auxiliary outputs 1, 2, and 3 for non-safety functions only, such as convenience in automation.
They cannot protect personnel from a moving hazard.
Failure to comply with these instructions will result in death or serious injury.
Table 4-12. Switch 8 Settings (S101): Auxiliary Output 1 Response to Interrupted Stroke
Settings
Auxiliary Output 1 State Change
OPEN
Normal operation (Default). Aux. Output 1 turns “off” when one
of the following occurs:
an Interrupted Stroke* condition
a fault condition (error code displays)
an open E-stop string
a light curtain interruption while press is running
CLOSED
Aux. Output 1 stays “on” during Interrupted Stroke if no fault
condition or E-stop occurs, turns “off” when one of the
following occurs:
a fault condition (error code displays)
an open E-stop string
a light curtain interruption while press is running
DANGER
!
Summary of Contents for SmartPAC 2
Page 2: ......
Page 4: ......
Page 6: ......
Page 28: ...1128600 SmartPAC 2 with WPC 2000 Integration User Manual xxii Table of Contents ...
Page 44: ...1128600 SmartPAC 2 with WPC 2000 Integration User Manual 1 16 Introduction ...
Page 186: ...1128600 SmartPAC 2 with WPC 2000 Integration User Manual 3 26 Keyboard Displays Etc ...
Page 440: ...1128600 SmartPAC 2 with WPC 2000 Integration User Manual D 12 Updating SmartPAC 2 Firmware ...
Page 478: ...1128600 SmartPAC 2 with WPC 2000 Integration User Manual G 6 Replacing SmartPAC 2 PC Board ...
Page 548: ...1128600 SmartPAC 2 with WPC 2000 Integration User Manual GL 8 Glossary ...
Page 558: ...1128600 SmartPAC 2 with WPC 2000 Integration User Manual IN 10 Index ...
Page 560: ......
Page 562: ......
Page 564: ......
Page 566: ......
Page 568: ......
Page 570: ......
Page 572: ......
Page 574: ......
Page 576: ......
Page 577: ......
Page 578: ...APPROVALS SCALE C SIZE TITLE SHEET OF DRAWING NUMBER REV ...
Page 579: ...APPROVALS SCALE C SIZE TITLE SHEET OF DRAWING NUMBER REV ...
Page 580: ...APPROVALS SCALE C SIZE TITLE SHEET OF DRAWING NUMBER REV ...
Page 581: ...APPROVALS SCALE C SIZE TITLE SHEET OF DRAWING NUMBER REV ...
Page 582: ......
Page 583: ......
Page 584: ......
Page 585: ......
Page 586: ......
Page 587: ......
Page 588: ......
Page 589: ......
Page 590: ......
Page 591: ......
Page 592: ......
Page 593: ......
Page 594: ......
Page 595: ......
Page 596: ......
Page 597: ......
Page 598: ......
Page 599: ......
Page 600: ......
Page 601: ......
Page 602: ......
Page 603: ......
Page 604: ......