List of parameters
Parameter
1-287
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description:
Displays the receive errors at the commissioning interface (RS232).
Index:
[0] = Number of error-free telegrams
[1] = Number of rejected telegrams
[2] = Number of framing errors
[3] = Number of overrun errors
[4] = Number of parity errors
[5] = Number of starting character errors
[6] = Number of checksum errors
[7] = Number of length errors
Description:
Sets the baud rate for the fieldbus interface USS.
Value:
4:
2400 baud
5:
4800 baud
6:
9600 baud
7:
19200 baud
8:
38400 baud
9:
57600 baud
10:
76800 baud
11:
93750 baud
12:
115200 baud
13:
187500 baud
Note:
Fieldbus SS: Fieldbus interface
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
The parameter is set to the factory setting when the protocol is reselected.
Description:
Displays or sets the address for the fieldbus interface USS.
The address can be set as follows:
1) Using the address switch on the Control Unit.
--> p2021 displays the address setting.
--> A change only becomes effective after a POWER ON.
r2019[0...7]
Comm int error statistics / Comm err
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
-
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
p2020
Field bus interface baud rate / Field bus baud
CU_S110-DP
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
4 13
8
p2021
Field bus interface address / Field bus address
CU_S110-DP
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 31
0