Faults and alarms
List of faults and alarms
3-1078
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
F07460
EPOS: End of reference cam not found
Message value:
-
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
During the search for reference, when the axis reached the zero mark it also reached the end of the traversing range
without detecting an edge at the binector input "reference cam" (BI: p2612).
Maximum traversing range: -2147483648 [LU] ... -2147483647 [LU]
Remedy:
- check the "reference cam" binector input (BI: p2612).
- repeat the search for reference.
See also: p2612 (EPOS search for reference, reference cam)
A07461
EPOS: Reference point not set
Message value:
-
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
NONE
Acknowledge:
NONE
Cause:
When starting a traversing block/direct setpoint input, a reference point is not set (r2684.11 = 0).
Remedy:
Reference the system (search for reference, flying referencing, set reference point).
A07462
EPOS: Selected traversing block number does not exist
Message value:
%1
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
NONE
Acknowledge:
NONE
Cause:
A traversing block selected via BI: p2625 to BI: p2630 was started via BI: p2631 = 0/1 edge "Activate traversing task".
- the number of the started traversing block is not contained in p2616[0...n].
- the started traversing block is suppressed.
Alarm value (r2124, interpret decimal):
Number of the selected traversing block that is also not available.
Remedy:
- correct the traversing program.
- select an available traversing block number.
A07463 (F)
EPOS: External block change not requested in the traversing block
Message value:
%1
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
NONE
Acknowledge:
NONE
Cause:
For a traversing block with the block change enable CONTINUE_EXTERNAL_ALARM, the external block change
was not requested.
Alarm value (r2124, interpret decimal):
Number of the traversing block.
Remedy:
Resolve the reason as to why the edge is missing at binector input (BI: p2632).
Reaction upon F:
OFF1
Acknowl. upon F:
IMMEDIATELY
F07464
EPOS: Traversing block is inconsistent
Message value:
%1
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The traversing block does not contain valid information.
Alarm value (r2124, interpret decimal):
Number of the traversing block with invalid information.
Remedy:
Check the traversing block and where relevant, take into consideration alarms that are present.