Parameter
List of parameters
1-632
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Dependency:
Refer to: p10001, p10003, p10007, p10047
Note:
The test stop is only performed if the safety output of the Control Unit is being used (see p10042).
Description:
Sets the test stop mode for the safety digital output (F-DO)
Value:
1:
Test mode 1 evaluation of int. diagnostic signal (passive load)
2:
Test mode 2 read back F-DO in DI (relay circuit)
3:
Test mode 3 read back F-DO in DI (actuator with feedback signal)
Dependency:
Refer to: p10001, p10003, p10007, p10046
Note:
The test stop is only performed if the safety output is being used (see p10042).
Description:
Displays the monitoring status of the fail-safe digital inputs (F-DI).
The F-DIs that are being used by the Safety Integrated functions are displayed.
If the module used has fewer than 3 F-DIs, "Freely available" is displayed for the F-DIs which are not in use.
Dependency:
p10006 / p10106
p10022 / p10122
p10023 / p10123
p10024 / p10124
p10025 / p10125
p10026 / p10126
p10027 / p10127
p10028 / p10128
p10030 / p10130
p10031 / p10131
p10036 / p10136
p10050 / p10150
Refer to: r10149
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Test F-DO 0
Test active
No test
-
p10047
SI F-DO test stop mode / SI F-DO test mode
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0001 bin
0011 bin
0010 bin
r10049
SI F-DI monitoring status (processor 1) / SI F-DI status P1
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
F-DI 0
Safety monitored
Freely available
-
01
F-DI 1
Safety monitored
Freely available
-
02
F-DI 2
Safety monitored
Freely available
-