Parameter
List of parameters
1-530
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Note:
For the commissioning software, after changing over the axis type, the units dependent on the axis type are only
updated after a project upload.
A change only becomes effective after a POWER ON.
Description:
Sets the function specification for the safe motion monitoring.
Value:
0:
Safety with encoder
1:
Safety without encoder
3:
Safety without encoder with accel_monitoring/delay time
Dependency:
Refer to: C30711
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Description:
Sets the function configuration for the safe motion monitoring functions.
Dependency:
Refer to: C01711
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
Re bit 00:
When the function is activated, a safety-relevant acknowledgement (internal event acknowledge) can be performed
by selecting/deselecting STO.
Re bit 01:
When the function is activated, the active setpoint velocity limit (CO: r9733) is set to zero when STOP F is active.
Re bit 02:
This bit defines the type of motor, which the sensorless safety technology evaluates.
For bit = 0, the sensorless motion monitoring function calculates the actual velocity for an induction motor.
For bit = 1, an actual velocity is calculated for a synchronous motor. This value depends on the setting in p0300.
Bit = 0 should be set if no motor is defined (p0300 = 0).
Description:
Sets the behavior of safety functions and their feedback during pulse suppression in encoderless operation.
p9306
SI Motion function specification (processor 2) / SI Mtn fct spec P2
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 3
0
p9307
SI Motion function configuration (processor 2) / SI Mtn config P2
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0000
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Extended message acknowledgement
Yes
No
-
01
Setpoint velocity limit for STOP F
No
Yes
-
02
Motor type sensorless actual value sensing Synchronous motor
Induction motor
-
p9309
SI Motion behavior during pulse suppression (processor 2) / SI Mtn behav IL P2
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-
-
0000 0000 1111 1111 bin