F30662
Error in internal communications
Message value:
%1
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
A module-internal communication error has occurred.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (power off/on).
- upgrade firmware to later version.
- contact the Hotline.
F30664
Error while booting
Message value:
%1
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
An error has occurred during booting.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (power off/on).
- upgrade firmware to later version.
- contact the Hotline.
F30665
SI MM: System is defective
Message value:
%1
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A system defect was detected before the last boot or in the actual one. The system might have been rebooted (reset).
Fault value (r0949, interpret hexadecimal):
200000 hex, 400000 hex:
- Fault in the actual booting/operation.
2 hex:
- parameters p9500 and p9300 are not the same (if Safety message C30711 is displayed at the same time).
Additional values:
- defect before the last time that the system booted.
Remedy:
- carry out a POWER ON (power off/on).
- upgrade firmware to later version.
- contact the Hotline.
For fault value = 2:
- check parameters p9500 and p9300 to see if they are the same (if Safety message C30711 is displayed at the same
time).
Re fault value = 400000 hex:
- ensure that the Control Unit is connected to the Power Module.
A30666 (F)
SI Motion MM: Steady-state (static) 1 signal at the F-DI for safety-relevant acknowl-
edgement
Message value:
-
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
NONE
Acknowledge:
NONE
Cause:
A logical 1 signal is present at the F-DI configured in p10106 for more than 10 seconds.
If, at the F-DI no acknowledgment was performed for safe acknowledgment, then a steady-state logical and 0 signal
must be present. This avoids unintentional safety-relevant acknowledgement (or the "Internal Event Acknowledge"
signal) if a wire breaks or one of the two digital inputs bounces.