Parameter
List of parameters
1-140
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description:
Sets the overvoltage protection for synchronous motors in the field-weakening range.
Value:
0:
No measure
1:
Voltage Protection Module (VPM)
Dependency:
Refer to: p0316, p1082, p1231, p9601, p9801
Refer to: F07432, F07906, F07907
Notice:
When the speed limiting is removed, the user is responsible for implementing a suitable overvoltage protection.
Note:
In the field-weakening range, synchronous motors can, when a fault condition exists, generate high DC link volt-
ages. The following possibilities exist to protect the drive system from being destroyed due to overvoltage:
- limit the maximum speed (p1082) without any additional protection.
The maximum speed without protection is calculated as follows:
p1082 [rpm] <= 11.695 * r0297/p0316 [Nm/A]
- use a Voltage Protection Module (VPM) in conjunction with the function "Safe Torque Off" (p9601, p9801).
When a fault condition exists, the VPM short-circuits the motors. During the short-circuit, the pulses must be sup-
pressed - this means that the terminals for the function "Safe Torque Off" must be connected to the VPM.
- activating the internal voltage protection (IVP) with p1231 = 3.
Description:
Displays the operating hours for the corresponding motor.
The motor operating time counter continues to run when the pulses are enabled. When the pulse enable is with-
drawn, the counter is held and the value saved.
Dependency:
Refer to: p0651
Refer to: A01590
Note:
The operating hours counter in p0650 can only be reset to 0. In this case, p0651 is automatically set to 0.
For p0651 = 0, the operating hours counter is disabled.
The operating hours counter only runs with motor data set 0 and 1 (MDS).
Description:
Sets the service/maintenance intervals in hours for the appropriate motor.
An appropriate fault is output when the operating hours set here are reached.
Dependency:
Refer to: p0650
Refer to: A01590
Note:
For p0651 = 0, the operating hours counter is disabled.
The operating hours counter only runs with motor data set 0 and 1 (MDS).
p0643[0...n]
Overvoltage protection for synchronous motors / Overvolt_protect
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Integer16
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
p0650[0...n]
Actual motor operating hours / Mot t_oper act
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [h]
4294967295 [h]
0 [h]
p0651[0...n]
Motor operating hours maintenance interval / Mot t_op maint
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [h]
150000 [h]
0 [h]