Parameter
List of parameters
1-216
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description:
Sets the automatic restart mode (AR).
Value:
0:
Inhibit automatic restart
1:
Acknowledge all faults without restarting
4:
Restart after line supply failure w/o additional start attempts
6:
Restart after fault with additional start attempts
14:
Restart after line supply failure following man. acknowledgment
16:
Restart after fault following manual acknowledgment
Dependency:
The automatic restart requires an active ON command (e.g., via a digital input). If, for p1210 > 1, there is no active
ON command, then the automatic restart is interrupted.
When using an Operator Panel in the LOCAL mode, then there is no automatic start.
For p1210 = 14, 16, a manual acknowledgement is required for an automatic restart.
Refer to: p0840, p0857
Refer to: F30003
Danger:
If the automatic restart is activated (p1210 > 1) if there is an ON command (refer to p0840), the drive is powered up
as soon as any fault messages that are present can be acknowledged. This also occurs after the line supply returns
or the Control Unit boots if the DC link voltage is again present or the feedback of the line supply infeed (refer to
p0864) is again available. This automatic power-up sequence can only be interrupted by withdrawing the ON com-
mand.
Caution:
A change is only accepted and made in the state "initialization" (r1214.0) and "wait for alarm" (r1214.1). When faults
are present, therefore, the parameter cannot be changed.
For p1210 > 1, the motor is automatically started.
Note:
Re p1210 = 1:
Faults that are present are automatically acknowledged. If new faults occur after a successful fault acknowledg-
ment, then these are also automatically acknowledged again. p1211 has no influence on the number of acknowl-
edgment attempts.
Re p1210 = 4:
An automatic restart is only carried out if fault F30003 occurred at the Motor Module or a 1 signal is present at
binector input p1208[1]. If additional faults are present, then these faults are also acknowledged and when success-
ful, starting continues. If the 24 V Control Unit power supply fails, then this is interpreted as a line supply failure.
Re p1210 = 6:
An automatic restart is carried out if any fault has occurred or there is a 1 signal at binector input p1208[0].
Re p1210 = 14:
As for p1210 = 4. However, faults that are present must be manually acknowledged.
Re p1210 = 16:
As for p1210 = 6. However, faults that are present must be manually acknowledged.
Description:
Sets the start attempts of the automatic restart function for p1210 = 4, 6.
Dependency:
Refer to: p1210, r1214
Refer to: F07320
Caution:
A change is only accepted and made in the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
p1210
Automatic restart, mode / AR mode
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Functions
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 16
0
p1211
Automatic restart, start attempts / AR start attempts
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
Functions
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 10
3