Parameter
List of parameters
1-70
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description:
Enter the inductance of a filter connected at the power unit output.
Dependency:
This parameter is automatically pre-set when you select a filter via p0230 if a SIEMENS filter is defined for the
power unit.
Note:
The parameter cannot be changed if the power unit has an internal sine-wave filter.
Description:
Enters the capacitance of a sine-wave filter connected at the power unit output.
Dependency:
This parameter is automatically pre-set when you select a filter via p0230 if a SIEMENS filter is defined for the
power unit.
Note:
The parameter value includes the sum of all of the capacitances of a phase connected in series (phase - ground).
The parameter cannot be changed if the power unit has an internal sine-wave filter.
Description:
Displays the internal resistance of the power unit (IGBT and line resistance).
Note:
For a parallel circuit, the value corresponds to the resistance of a power unit.
Description:
Sets the cooling type for booksize compact power units.
This therefore defines whether for these power units, the internal air cooling is shut down and instead, the "Cold-
Plate" cooling type is used.
Value:
0:
Air cooling int
1:
Cold-Plate
Note:
For booksize compact power units, there is a 4 at the 5th position in the Order No.
The parameter is irrelevant for all other power unit types.
p0233
Power unit motor reactor / PU mot reactor
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
C2(2), U, T
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dynamic index:
-
Func. diagram:
-
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 [mH]
1000.000 [mH]
0.000 [mH]
p0234
Power unit sine-wave filter capacitance / PU sine filter C
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
C2(2), U, T
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dynamic index:
-
Func. diagram:
-
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 [µF]
1000.000 [µF]
0.000 [µF]
r0238
Internal power unit resistance / PU R internal
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dynamic index:
-
Func. diagram:
-
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- [ohm]
- [ohm]
- [ohm]
p0249
Power unit cooling type / PU cool type
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
C2(1, 2)
Calculated:
-
Access level:
4
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0