List of parameters
Parameter
1-397
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description:
Sets the monitoring window of the actual position after the fixed stop is reached.
Dependency:
Refer to: r2526, r2683
Refer to: F07484
Note:
If, after the fixed stop is reached, the end stop shifts in either the positive or negative direction by more than the
value set here, then BO: r2526.5 is set to 1 and an appropriate message is output.
Description:
Sets the signal source for the feedback signal "fixed stop reached".
BI: p2637 = 1 signal
Fixed stop is reached.
BI: p2637 = 0 signal
Fixed stop is not reached.
Dependency:
Refer to: r2526, p2634
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
The identification of "fixed stop reached" is, for the factory setting, dependent on the signal BO: r2526.4 (fixed stop
reached). This signal is influenced via p2634 (EPOS fixed stop, maximum following error).
Description:
Sets the signal source for the feedback signal "fixed stop outside the monitoring window".
BI: p2638 = 1 signal
Fixed stop is located outside the monitoring window.
BI: p2638 = 0 signal
Fixed stop is inside the monitoring window.
Dependency:
Refer to: r2526, p2635
Note:
The identification of "fixed stop outside the monitoring window" is, for the factory setting, dependent on signal BO:
r2526.5 (fixed stop outside window). This signal is influenced via p2635 (EPOS fixed stop monitoring window).
p2635
EPOS fixed stop monitoring window / Fixed stop monit
SERVO_S110-CAN
(Pos ctrl),
SERVO_S110-DP
(Pos ctrl),
SERVO_S110-PN
(Pos ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
1
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
3617, 4025
P-Group:
Closed loop position control
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [LU]
2147482647 [LU]
100 [LU]
p2637
BI: EPOS fixed stop reached / Fixed stop reached
SERVO_S110-CAN
(EPOS),
SERVO_S110-DP
(EPOS),
SERVO_S110-PN
(EPOS)
Can be changed:
T
Calculated:
-
Access level:
1
Data type:
Unsigned32 / Binary
Dynamic index:
-
Func. diagram:
3616, 3617
P-Group:
Basic positioner
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
2526.4
p2638
BI: EPOS fixed stop outside the monitoring window / Fixed stop outside
SERVO_S110-CAN
(EPOS),
SERVO_S110-DP
(EPOS),
SERVO_S110-PN
(EPOS)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
-
Func. diagram:
3616, 3617
P-Group:
Basic positioner
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
2526.5