Parameter
List of parameters
1-172
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description:
Sets the delay time for the control command of the power unit and a line contactor, if used.
Note:
This means that it is possible to realize a shifted (delayed) pre-charging or power-on using a single ON command.
When the infeed units are active, before the line contactor is closed, an offset adjustment of the current measure-
ment is carried out for a duration of 120 ms (p3491).
Description:
Displays the status and control words of the drive coupling.
Note:
Re bit 00:
Bit 0 signals that the infeed is ready.
When the operating signal is transferred via BO: r0863.0 this allows several drives to start (run-up) staggered over
time when they are simultaneously powered up.
To realize this, the following connections/interconnections are required:
Drive 1: Internconnect BI: p0864 with BO: r0863.0 of the infeed
Drive 2: Internconnect BI: p0864 with BO: r0863.0 of drive 1
Drive 3: Internconnect BI: p0864 with BO: r0863.0 of drive 2, etc.
The first drive only transfers the operating signal to the next drive after it has reached its ready condition.
Re bit 01:
Bit 1 is used to control an external line contactor.
Re bit 02:
This bit only signals line supply failure for Active Infeed (A_INF) and Smart Infeed (S_INF).
p0862
Power unit ON delay / PU t_on
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dynamic index:
-
Func. diagram:
2610, 8732,
8832, 8932
P-Group:
Commands
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [ms]
65000 [ms]
0 [ms]
r0863.0...2
CO/BO: Drive coupling status word/control word / CoupleZSW/STW
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
Commands
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Closed-loop control operation
Yes
No
2610,
6495,
8732,
8832,
8932,
9794
01
Energize contactor
Yes
No
2610,
2634,
8732,
8734,
8832,
8834,
8932,
8934
02
Infeed line supply failure
Yes
No
-