
List of parameters
Parameter
1-587
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
87:
[57 hex] Start copy function SI parameters
208:
[D0 hex] Start copy function SI basic parameters
Note:
Re value = 57 hex and D0 hex:
The value can only be set if the safety commissioning mode is set and the Safety Integrated password was entered.
Re value = D0 hex:
The following parameters are copied after starting the copy function:
p9601/p9801, p9602/p9802, p9610/9810, p9650/p9850, p9652/p9852, p9658/p9858
Description:
Setting to transfer the reference checksums from the associated actual checksums after changes (SI parameters,
hardware).
After transferring the reference checksums, parameters are automatically reset to zero.
Value:
0:
[00 hex] Data unchanged
172:
[AC hex] Acknowledge data change complete
220:
[DC hex] Acknowledge SI basic parameter change
236:
[EC hex] Acknowledge hardware CRC
Dependency:
Refer to: r9398, p9399, r9728, p9729, r9798, p9799, r9898, p9899
Note:
Re value = AC and DC hex:
These values can only be set if the safety commissioning mode is set and the Safety Integrated password was
entered.
Description:
Sets the signal source for the test stop of the safety-relevant motion monitoring functions.
Caution:
Before setting the signal source in p9705 it must be ensured that the signal source is at a logical 0.
If, in the Safety commissioning mode, the signal source in p9705 is set - and it already has a logical 1 - then a test
stop is immediately initiated and the messages C01711/C30711 are output with message value 1005.
Notice:
It is not permissible to use TM54F inputs to start the test stop.
Description:
Displays result list 1 that, for the crosswise data comparison between the monitoring channels, led to the fault.
Index:
[0] = Result list, second channel
[1] = Result list, drive
p9701
Acknowledge SI motion data change / Ackn SI Mtn dat
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
C2(95), U, T
Calculated:
-
Access level:
3
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0000 hex
00EC hex
0000 hex
p9705
BI: SI Motion: Test stop signal source / SI Mtn test stop
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
r9710[0...1]
SI Motion diagnostics result list 1 / SI Mtn res_list 1
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Actual value > upper limit SOS
Yes
No
-
01
Actual value > lower limit SOS
Yes
No
-
02
Actual value > upper limit, SLP1
Yes
No
-