
Parameter
List of parameters
1-238
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Note:
Re bit 04:
The following conditions must be fulfilled to set to 1:
- CI: p1190 and CI: p1191 must be interconnected with a signal source that is not equal to zero.
- it is not permissible that OFF1, OFF3 or STOP2 are active.
- it is not permissible that the motor data identification is active.
- Master control must not be active.
The following conditions can mean that the DSC function is not active in spite of the fact that the bit is set:
- clock-cycle synchronous operation is not selected (r2054 not equal to 4).
- the PROFIBUS is not clock-cycle synchronous (r2064[0] not equal to 1).
- DSC is not switched on at the control side; this means that KPC = 0 is transferred as the value at CI: p1191.
Description:
Displays the current controller status word.
Note:
The set current limit is taken into account in upstream torque limiting. Bits 6, 7, and 8 are, therefore, only set in the
event of overshoots on account of the current setpoint filter.
Description:
Setting for activating/de-activating the speed setpoint filter.
Recommend.:
If only one filter is required, filter 1 should be activated and filter 2 de-activated, to avoid excessive processing time.
Dependency:
The individual speed setpoint filters are parameterized as of p1415.
Description:
Sets the type for speed setpoint filter 1.
11
Speed setpoint limited
Yes
No
-
13
Encoderless operation due to a fault
Yes
No
-
r1408.0...9
CO/BO: Status word current controller / ZSW I_ctrl
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
2530, 5040
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Closed-loop current control
Active
Not active
-
04
Limit Ud
Active
Not active
-
05
Limit Vq
Active
Not active
-
06
Positive limiting Iq
Active
Not active
-
07
Negative limiting Iq
Active
Not active
-
08
Limit iq_set
Active
Not active
-
09
Limit id_set
Active
Not active
-
p1414[0...n]
Speed setpoint filter activation / n_set_filt act
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
DDS, p0180
Func. diagram:
5020
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0000
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Activate filter 1
Yes
No
-
p1415[0...n]
Speed setpoint filter 1 type / n_set_filt 1 typ
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Integer16
Dynamic index:
DDS, p0180
Func. diagram:
5020
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 2
0