
Parameter
List of parameters
1-558
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
The encoder that is used for the safe motion monitoring functions on processor 1 must be parameterized in this
parameter.
Dependency:
Refer to: r0474, p9315
Note:
For safe functions that are not enabled (p9501 = 0), the following applies:
- p9515 is automatically set the same as p0474 when the system boots.
For safety functions that are enabled (p9501 > 0), the following applies:
- p9515 is checked to see that it matches p0474.
Description:
Sets the configuration for the motor encoder and position actual value.
The encoder that is used for the safe motion monitoring functions on processor 1 must be parameterized in this
parameter.
Dependency:
Refer to: p0404, p0410
Refer to: F01671
Note:
For safe functions that are not enabled (p9501 = 0), the following applies:
- p9516.0 is automatically set the same as p0404.0 when the system boots.
- p9516.1 is automatically set the same as p0410.1 when the system boots.
For safety functions that are enabled (p9501 > 0), the following applies:
- p9516.1 is checked to identify whether it coincides with p0410.1.
Description:
Sets the grid division for a linear motor encoder.
The encoder that is used for the safe motion monitoring functions on processor 1 must be parameterized in this
parameter.
Dependency:
Refer to: p9516
Refer to: F01671
Note:
For safety functions that have not been enabled (p9501 = 0), the following applies: When booting p9517 is automat-
ically set the same as p0407.
For safety functions that are enabled (p9501 > 0), the following applies: p9517 is checked whether it coincides with
p0407.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Incrementer
Yes
No
-
01
Encoder CRC least significant byte first
Yes
No
-
02
Redundant coarse position val. most signifi-
cant bit left-aligned
Yes
No
-
16
DRIVE-CLiQ encoder
Yes
No
-
p9516
SI Motion encoder configuration safety functions (processor 1) / SI Mtn enc_cfg P1
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0000
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Motor encoder, rotating/linear
Linear
Rotating:
-
01
Position actual value, sign change
Yes
No
-
p9517
SI Motion linear scale grid division (processor 1) / SI Mtn grid P1
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [nm]
250000000.00 [nm]
10000.00 [nm]