Parameter
List of parameters
1-498
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description:
Displays all of the devices connected to the CAN bus after run-up.
r8600
= 00000000 hex: No drive recognized.
= 00020192 hex: 1 Servo drive
Note:
Corresponds to the CANopen object 1000 hex.
For each detected drive, the device type is displayed in object 67FF hex.
Description:
Displays the error register for CANopen.
Bit 0: Generic error
0 signal: No error present.
1 signal: Generic error present.
Bit 1 ... 3: Not supported (always a 0 signal)
Bit 4: Communications error
0 signal: There is no message in the range 8700 ... 8799.
1 signal: There is at least one message (fault or alarm) in the range 8700 ... 8799.
Bit 5 ... 6: Not supported (always a 0 signal)
Bit 7:; Fault outside the range 8700 ... 8799
0 signal: There is no fault outside the range 8700 ... 8799.
1 signal: There is at least one fault outside the range 8700 ... 8799.
Note:
Corresponds to the CANopen object 1001 hex.
Description:
Sets the SYNC object parameter for the following CANopen objects:
- 1005 hex: COB-ID
Note:
SINAMICS operates as SYNC load.
COB-ID: CAN object identification
r8600
CAN device type / Device type
CU_S110-CAN
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
-
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
r8601
CAN error register / Error register
CU_S110-CAN
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned8
Dynamic index:
-
Func. diagram:
-
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
p8602
CAN SYNC object / SYNC object
CU_S110-CAN
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
-
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0000 hex
FFFF FFFF hex
0080 hex