MC1000 FAULT HISTORY

Parameter 70 - FAULT HISTORY stores the last eight faults that tripped
the drive.  The FAULT HISTORY indicates the number of the fault
(number 1 is the most recent fault), the fault message, and the status of
the drive at the time of the fault.  An example is shown below:

MC1000 FAULT MESSAGES

FAU

LT

DES

CRIP

TION

OUTPUT

LO VOLTS

HI VOLTS

HI TEMP

OVERLOAD

PWR TRAN

PWR SAG

LANGUAGE

EXTERNAL

DB ERROR

CONTROL

INTERNAL

INTERN (#)

Output Transistor fault;  Output current exceeded
200%.  May be ground fault or short circuit.
Low DC Bus Voltage fault:  DC bus voltage
dropped below 60%.  May be low line voltage.
High DC Bus Voltage fault:  DC bus voltage
exceeded 120%.  May be overhauling load.
High Temperature fault:  Heatsink or ambient
temperature too high.
Current Overload fault:  Output current exceeded
100% for too long.  VFD may be undersized.
Power Transient fault.

Power Sag fault:  New control board installed.
Perform factory reset using Parameter 65.
Language EEPROM fault.

External fault:  TB-13D activated (Parameter 50).

Dynamic Brake fault:  DB Resistors overloaded.

Control Board fault:  New software installed.
Perform factory reset using Parameter 65.
Internal fault.

Internal fault.

In the example above, the second fault is being viewed, which is an
OUTPUT fault that ocurred while the drive was accelerating.

2  OUTPUT     ACCEL

   FAULT
NUMBER

   FAULT
MESSAGE

DRIVE
STATUS

MC1000 PARAMETERS

QRM1-OBOC

NOTE 1:  REFER TO THE MC1000 MANUAL.
NOTE 2:  THESE PARAMETERS ARE VIEW-ONLY.

AC Technology Corporation

660 Douglas St, Uxbridge, MA 01569

800-217-9100, FAX: 508-278-7873

www.actechdrives.com

NOTE:

  Before installing and operating the MC1000 drive,

please read and become familiar with the MC1000 Series
Installation and Operation Manual.

MC1000 Series

Quick Reference Guide

RUN     >    60.00  HZ

Intelligent Drive

START

STOP

ENTER

AUTO

MAN

PROG

RUN

FWD
REV

CONTROL

LOCAL

30

FAULT

HISTORY

(NOTE 2)

70

UNITS

HERTZ

31

SPEED DP

XXXXX

33

LOAD MLT

100 %

34

SPEED #4

20.00 HZ

4

SPEED #3

20.00 HZ

3

SPEED #2

20.00 HZ

2

SPEED #1

20.00 HZ

1

LINE VOLTS

AUTO

0

HZ MULT

1.00

32

SKIP #1

.00 HZ

5

SKIP #2

.00 HZ

6

BAND WID

1.00 HZ

7

TB5 MAX

60.00 HZ

40

ACCEL

30.0 SEC

8

AIN FLTR

0.02 SEC

41

DECEL

30.0 SEC

9

TB10A OUT

NONE

42

MIN FRQ

.50 HZ

10

@TB10A

60.00 HZ

43

MAX FRQ

60.00 HZ

11

TB10B OUT

NONE

44

DC BRAKE

.0 VDC

12

@TB10B

125 %

45

DC TIME

.0 SEC

13

TB13A

NONE

47

DYN BRAKE

OFF

14

TB13B

NONE

48

CURRENT

180 %

16

TB13C

NONE

49

MOTOR OL

100 %

17

TB13D

EXT FAULT

50

BASE

60.00 HZ

18

TB14 OUT

NONE

52

FX BOOST

(NOTE 1)

19

TB15 OUT

NONE

53

AC BOOST

.0 %

20

RELAY

NONE

54

SLIP CMP

.0 %

21

SERIAL

DISABLE

57

TORQUE

CONSTANT

22

ADDRESS

30

58

CARRIER

2.5 KHZ

23

PASSWORD

0019

61

START

NORMAL

25

SOFTWARE

(NOTE 2)

63

STOP

COAST

26

MONITOR

ON

64

ROTATION

FORWARD

27

PROGRAM

RESET 60

65

AUTO / MAN

BOTH

28

HISTORY

MAINTAIN

66

MANUAL

KEYPAD

29

LANGUAGE

ENGLISH

69

CONTRAST

MED

35

SLEEP TH

.00 HZ

36

SLEEP DL

30.0 SEC

37

TB5 MIN

.00 HZ

39

PARAMETER

NAME

FACTORY

DEFAULT

NO.

PARAMETER

NAME

FACTORY

DEFAULT

NO.

mc series