![background image](http://html1.mh-extra.com/html/omron/cp1h-cpu-05-2006/cp1h-cpu-05-2006_operation-manual_742082626.webp)
595
Connections to Serial Communications Option Boards
Appendix F
Wiring Connectors
Use the following steps to wire connectors.
See the following diagrams for the length of the cable portion to be cut in each step.
Shield Connected to Hood (FG)
1.
Cut the cable to the required length.
2.
Remove the specified length of the sheath from the cable using a knife. Be careful not to scratch the braided
shield.
3.
Trim off the braided shield using scissors so that the remaining shield length is 10 mm.
4.
Remove the insulation from each conductor using a stripper so that the exposed conductor length is 5 mm.
5.
Fold back the braided shield.
6.
Wrap aluminum foil tape around the folded shield.
Shield Not Connected to Hood (FG)
1.
Cut the cable to the required length.
2.
Remove the specified length of the sheath from the cable using a knife. Be careful not to scratch the braided
shield.
3.
Trim off all the braided shield using scissors.
4.
Remove the insulation from each conductor using a stripper so that the exposed conductor length is 5 mm.
25 mm (RS-422A)
40 mm (RS-232C)
10 mm
5 mm
Aluminum foil tape
25 mm (RS-422A)
40 mm (RS-232C)
5 mm
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...
Page 667: ...636 Revision History...