Section 4-4
Note
The built-in analog outputs will operate as follows when the operating mode is
switched between RUN or MONITOR mode and PROGRAM mode:
Note
Control of the built-in analog outputs will temporarily stop when Memory Cas-
sette data is being transferred or verified. Therefore, if the operating mode is
switched between PROGRAM and RUN or MONITOR mode when the built-in
analog output is being used and the I/O Memory Hold Bit is set to ON to retain
analog values output externally, the values will change; the analog values out-
put externally will not be retained while Memory Cassette data is being trans-
ferred or verified. The analog output values will return to the original retained
values when the transfer or verification has been completed.
4-4
Data Link Area
Data Link Area addresses range from CIO 1000 to CIO 1199
(bits CIO 1000.00 to CIO 1199.15). Words in the Link Area are used for data
links when LR is set as the data link area for Controller Link Networks. It is
also used for PLC Links. Words in the Link Area can be used in the program
when LR is not set as the data link area for Controller Link Networks and PLC
Links are not used.
Data links can be generated automatically (using the same number of words
for each node) or manually. When a user defines the data links manually, any
number of words can be assigned to each node, and nodes can be made
receive-only or transmit-only. Refer to the Controller Link Units Operation
Manual (W309) for details.
Forcing Bit Status
Bits in the Data Link Area can be force-set and force-reset.
Links to C200HX/HG/HE,
C200HS, and C200H PLCs
Link Area words CIO 1000 to CIO 1063 in CP1H CPU Units correspond to
Link Relay Area words LR 0 to LR 63 for data links created in
C200HX/HG/HE(-Z) PLCs. When converting C200HX/HG/HE(-Z), C200HS,
or C200H programs for use in CP1H CPU Units, change addresses LR 0
through LR 63 to Link Area addresses CIO 1000 through CIO 1063.
I/O Memory Hold Bit
(A500.12)
Operation
OFF
The analog output values in the words allocated in
memory will be cleared and the 0000 hex will be output
for the output refresh.
ON
The analog output values in the words allocated in
memory will retain their values from right before the
operating mode was changed and the previous values
will be output for the output refresh.
Controller
Link Unit
CPU Unit
Linked words
Controller
Link Unit
CPU Unit
Controller
Link Unit
CPU Unit
Controller Link Network
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...
Page 667: ...636 Revision History...