49
Specifications
Section 2-2
Note
The above values are for a cold start at room temperature for an AC power
supply, and for a cold start for a DC power supply.
• A thermistor (with low-temperature current suppression characteristics) is
used in the inrush current control circuitry for the AC power supply. The
thermistor will not be sufficiently cooled if the ambient temperature is high
or if a hot start is performed when the power supply has been OFF for
only a short time, so in those cases the inrush current values may be
higher (as much as two times higher) than those shown above.
Always allow for this when selecting fuses and breakers for external cir-
cuits.
• A capacitor delay circuit is used in the inrush current control circuitry for
the DC power supply. The capacitor will not be charged if a hot start is
performed when the power supply has been OFF for only a short time, so
in those cases the inrush current values may be higher (as much as two
times higher) than those shown above.
Characteristics
Insulation resistance 20 M
Ω
min. (at 500 VDC) between the external
AC terminals and GR terminals
No insulation between primary and secondary
DC power supplies.
Dielectric strength
2,300 VAC 50/60 Hz for 1 min between the
external AC and GR terminals, leakage current:
5 mA max.
No insulation between primary and secondary
DC power supplies.
Noise resistance
Conforms to IEC 61000-4-4 2 kV (power supply line)
Vibration resistance
10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s
2
in X, Y, and Z directions for
80 minutes each (time coefficient of 8 minutes
×
coefficient factor of 10 = total time of 80 minutes)
Shock resistance
147 m/s
2
three times each in X, Y, and Z directions
Ambient operating
temperature
0 to 55
°
C
Ambient humidity
10% to 90% (with no condensation)
Atmosphere
No corrosive gas.
Ambient storage
temperature
−
20 to 75
°
C (excluding battery)
Terminal screw size
M3
Power interrupt time
10 ms min.
2 ms min.
Weight
740 g max.
590 g max.
560 g max.
Power supply
classification
AC power supply
DC power supply
Model numbers
• XA CPU Units
CP1H-XA40DR-A
• X CPU Units
CP1H-X40DR-A
• XA CPU Units
CP1H-XA40DT-D
CP1H-XA40DT1-D
• X CPU Units
CP1H-X40DT-D
CP1H-X40DT1-D
• Y CPU Units
CP1H-Y20DT-D
Type
X CPU Units
XA CPU Units
Y CPU Units
Model
CP1H-X40DR-A
CP1H-X40DT-D
CP1H-X40DT1-D
CP1H-XA40DR-A
CP1H-XA40DT-D
CP1H-XA40DT1-D
CP1H-Y20DT-D
Program capacity
20 Ksteps
Control method
Stored program method
I/O control method
Cyclic scan with immediate refreshing
Program language
Ladder diagram
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...
Page 667: ...636 Revision History...