430
Temperature Sensor Units
Section 7-5
Startup Operation
After power is turned ON, approximately 1 s is required for the first conversion
data to be stored in the input word. During that period, the data will be 7FFE.
Therefore, create a program as shown below, so that when operation begins
simultaneously with startup it will wait for valid conversion data.
Handling Unit Errors
• CPM1A Expansion Unit/Expansion I/O Unit errors are output to bits 0 to 6
of word A436. The bits are allocated from A436.00 in order starting from
the Unit nearest the CPU Unit. CPM1A-TS002 and CPM1A-TS102 Tem-
perature Sensor Units are allocated two bits each. Use these flags in the
program when it is necessary to detect Expansion Unit/Expansion I/O
Unit errors.
• When an error occurs, the Temperature Sensor Unit data becomes 7FFF
hex (the same as for an open-circuit detection). With an open-circuit
detection, it is not reflected in word A436.
Programming Example
1,2,3...
1.
The following programming example shows how to convert the input data
from 2 temperature sensor inputs to BCD and store the result in D0 and
D1.
(P_EQ)
1000.00
2
#7FFE
P_On
CMP(020)
Always ON
Temperature input data
output word
Initialization
Completed Flag
CP1H
CPM1A-TS001/101
Temperature Sensor Unit
Inputs
Outputs
CIO 0
CIO 1
CIO 100
CIO 101
CIO 2
CIO 3
None
Temperature unit setting:
0 (
°
C)
Two-decimal-place Mode:
0 (normal)
Input range setting:
1 (K: 0.0 to 500.0
°
C)
Input 0:
CIO 2
Input 1:
CIO 3
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...