123
Wiring CP1H CPU Units
Section 3-4
3-4-3
Wiring Safety and Noise Controls
I/O Signal Wiring
Whenever possible, place I/O signal lines and power lines in separate ducts or
conduits both inside and outside of the control panel.
If the I/O wiring and power wiring must be routed in the same duct, use
shielded cables and connect the shields to the GR terminal to reduce noise.
Inductive Loads
When an inductive load is connected to an I/O Unit, connect a surge suppres-
sor or diode in parallel with the load as shown below.
Note
Use surge suppressors and diodes with the following specifications.
Noise from External
Wiring
Take the following points into account when externally wiring I/O, power sup-
ply, and power lines.
• When multi-conductor signal cable is being used, avoid combining I/O
wires and other control wires in the same cable.
• If wiring racks are parallel, allow at least 300 mm between the Racks.
(1)
(2)
(1)
(2)
(1)
(2)
Suspended duct
In-floor duct
(1) = I/O cables
(2) = Power cables
Conduits
L
IN
COM
OUT
COM
OUT
COM
L
+
Diode
DC input
Relay output
Surge suppressor
Relay output or
transistor output
Diode
Surge Suppressor Specifications
Resistance: 50
Ω
Capacitance: 0.47
µ
F
Voltage: 200
V
Diode Specifications
Breakdown voltage:
3 times load voltage min.
Mean rectification current: 1 A
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...
Page 667: ...636 Revision History...