424
Temperature Sensor Units
Section 7-5
Part Names
Temperature Sensor Units
CPM1A-TS001/002/101/102
(1)
Temperature Sensor Input Terminals
Used to connect temperature sensors such as thermocouples or plati-
num resistance thermometers.
(2)
DIP Switch
Used to set the temperature unit (
°
C or
°
F) and the number of decimal
places used.
(3)
Rotary Switch
Used to set the temperature input range. Make the setting according to
the specifications of the temperature sensors that are connected.
(4)
Expansion I/O Connecting Cable
Connected to the expansion connector of a CP1H CPU Unit or a CPM1A
Expansion Unit or Expansion I/O Unit.The cable is included with the
Temperature Sensor Unit and cannot be removed.
Note
Do not touch the cables during operation. Static electricity may
cause operating errors.
(5)
Expansion Connector
Used for connecting CPM1A Expansion Units or Expansion I/O Units.
Main Specifications
Note
Accuracy for a K-type sensor at
−
100
°
C or less is ±4
°
C ±1 digit max.
(5) Expansion Connector
(1) Temperature Sensor Input Terminals
(4) Expansion I/O
Connector Cable
(3) Rotary Switch
(2) DIP Switch
Item
CPM1A-TS001
CPM1A-TS002
CPM1A-TS101
CPM1A-TS102
Temperature sensors
Thermocouples
Platinum resistance thermometer
Switchable between K and J, but same type
must be used for all inputs.
Switchable between Pt100 and JPt100, but
same type must be used for all inputs.
Number of inputs
2
4
2
4
Allocated input words
2
4
2
4
Max. number of Units
3
1
3
1
Accuracy
(The larger of
±
0.5% of converted value or
±
2
°
C)
±
1 digit max. (See note.)
(The larger of
±
0.5% of converted value or
±
1
°
C)
±
1 digit max.
Conversion time
250 ms for 2 or 4 input points
Converted temperature data
16-bit binary data (4-digit hexadecimal)
Isolation
Photocouplers between all temperature input signals
Current consumption
5 VDC: 40 mA max., 24 VDC: 59 mA max.
5 VDC: 54 mA max., 24 VDC: 73 mA max.
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...
Page 667: ...636 Revision History...