313
Pulse Outputs
Section 5-3
Preparation
■
PLC Setup
Note The interrupt input setting is read when the power supply is turned ON.
■
DM Area Settings
Speed Control Settings to Feed Wrapping Material to Initial Position
Positioning Control Settings for Wrapping Material
Setting details
Enable using built-in input IN0 as an interrupt input.
Setting details
Address
Data
Acceleration rate: 1,000 Hz/4 ms
D0
#03E8
Target frequency: 10,000 Hz
D1
#2710
D2
#0000
Setting details
Address
Data
Acceleration rate: 500 Hz/4 ms
D10
#01F4
Deceleration rate: 500 Hz/4 ms
D11
#01F4
Target frequency: 10,000 Hz
D12
#2710
D13
#0000
Number of output pulses: 5,000 pulses
D14
#1388
D15
#0000
Starting frequency: 0 Hz
D16
#0000
D17
#0000
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...
Page 667: ...636 Revision History...