289
Pulse Outputs
Section 5-3
• High-speed jog operation (CCW) will be executed from pulse output 1
while input 1.07 is ON.
Instructions Used
SPED(885) Starts and stops (immediate stop) the low-speed jog operations.
ACC(888)
Starts and stops (decelerate to a stop) the high-speed jog opera-
tions.
Preparation
■
PLC Setup
There are no settings that need to be made in the PLC Setup.
DM Area Settings
Settings to Control Speed while Jogging
(D0 to D1 and D10 to D15)
Target frequency
100,000 Hz
CW High-speed jog
(1.06)
CCW high-speed
jog (1.07)
Acceleration/de-
celeration rate
100 Hz/4 ms
Acceleration/de-
celeration rate
100 Hz/4 ms
Setting details
Address
Data
Target frequency (low speed): 1,000 Hz
D0
#03E8
D1
#0000
Acceleration rate: 100 Hz/4 ms
D10
#0064
Target frequency (high speed): 100,000 Hz
D011
#86A0
D12
#0001
Deceleration rate: 100 Hz/4 ms (Not used.)
D13
#0064
Target frequency (stop): 0 Hz
D14
#0000
D15
#0000
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...
Page 667: ...636 Revision History...