145
Overview of I/O Memory Area
Section 4-1
Timer PVs
The PVs are read and written as words (16 bits). The PVs count up or down
as the timer operates.
Counter Area (C)
There are two parts to the Counter Area: the Counter Completion Flags and
the Counter Present Values (PVs). Up to 4,096 counters with counter num-
bers C0 to C4095 can be used.
Counter Completion Flags
These flags are read as individual bits. A Completion Flag is turned ON by the
system when the corresponding counter counts out (i.e., when the set value is
reached).
Counter PVs
The PVs are read and written as words (16 bits). The PVs count up or down
as the counter operates.
Condition Flags
These flags include the Arithmetic Flags, such as the Error Flag and Equals
Flag, which indicate the results of instruction execution as well as the Always
ON and Always OFF Flags. The Condition Flags are specified with symbols
rather than addresses.
Clock Pulses
The Clock Pulses are turned ON and OFF by the CPU Unit’s internal timer.
These bits are specified with symbols rather than addresses.
Task Flag Area (TK)
A Task Flag will be ON when the corresponding cyclic task is in executable
(RUN) status and OFF when the cyclic task hasn’t been executed (INI) or is in
standby (WAIT) status.
Index Registers (IR)
Index registers (IR0 to IR15) are used to store PLC memory addresses (i.e.,
absolute memory addresses in RAM) to indirectly address words in I/O mem-
ory. The Index Registers can be used separately in each task or they can be
shared by all tasks.
Data Registers (DR)
Data registers (DR0 to DR15) are used together with Index Registers. When a
Data Register is input just before an Index Register, the content of the Data
Register is added to the PLC memory address in the Index Register to offset
that address. The Data Registers can be used separately in each task or they
can be shared by all tasks.
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...
Page 667: ...636 Revision History...