558
Auxiliary Area Allocations by Address
Appendix D
A531
A531.08 High-speed
Counter 0
Gate Bit
When a counter's Gate Bit is ON, the
counter's PV will not be changed
even if pulse inputs are received for
the counter.
When the bit is turned OFF again,
counting will restart and the high-
speed counter's PV will be refreshed.
When the reset method is set to
Phase-Z Software reset, the
Gate Bit is disabled while the corre-
sponding Reset Bit (A531.00 or
A531.01) is ON.
---
Retained
Cleared
---
---
A531.09 High-speed
Counter 1
Gate Bit
---
Retained
Cleared
---
---
A531.10 High-speed
Counter 2
Gate Bit
---
Retained
Cleared
---
---
A531.11 High-speed
Counter 3
Gate Bit
---
Retained
Cleared
---
---
A532
All
Interrupt
Counter 0
Counter SV
Used for interrupt input 0 in counter
mode.
Sets the count value at which the
interrupt task will start. Interrupt task
140 will start when interrupt counter
0 has counted this number of pulses.
Retained when operation starts.
---
Retained
Retained
---
---
A533
All
Interrupt
Counter 1
Counter SV
Used for interrupt input 1 in counter
mode.
Sets the count value at which the
interrupt task will start. Interrupt task
141 will start when interrupt counter
1 has counted this number of pulses.
---
Retained
Retained
---
---
A534
All
Interrupt
Counter 2
Counter SV
Used for interrupt input 2 in counter
mode.
Sets the count value at which the
interrupt task will start. Interrupt task
142 will start when interrupt counter
2 has counted this number of pulses.
---
Retained
Retained
---
---
A535
All
Interrupt
Counter 3
Counter SV
Used for interrupt input 3 in counter
mode.
Sets the count value at which the
interrupt task will start. Interrupt task
143 will start when interrupt counter
3 has counted this number of pulses.
---
Retained
Retained
---
---
A536
All
Interrupt
Counter 0
Counter PV
These words contain the interrupt
counter PVs for interrupt inputs oper-
ating in counter mode.
In increment mode, the counter PV
starts incrementing from 0. When the
counter PV reaches the counter SV,
the PV is automatically reset to 0.
In decrement mode, the counter PV
starts decrementing from the counter
SV. When the counter PV reaches
the 0, the PV is automatically reset to
the SV.
Cleared when operation starts.
---
---
Retained
Refresh-
ed when
interrupt
is gener-
ated.
Refresh-
ed when
INI(880)
instruc-
tion is
executed.
---
A537
All
Interrupt
Counter 1
Counter PV
---
---
---
A538
All
Interrupt
Counter 2
Counter PV
---
---
---
A539
All
Interrupt
Counter 3
Counter PV
---
---
---
A540
A540.00 Pulse Out-
put 0 Reset
Bit
The pulse output 0 PV (contained in
A276 and A277) will be cleared when
this bit is turned ON.
---
---
Cleared
---
A276 and
A277
A540.08 Pulse Out-
put 0 CW
Limit Input
Signal Flag
This is the CW limit input signal for
pulse output 0, which is used in the
origin search. To use this signal,
write the input from the actual sensor
as an input condition in the ladder
program and output the result to this
flag.
---
---
Cleared
---
---
A540.09 Pulse Out-
put 0 CCW
Limit Input
Signal Flag
This is the CCW limit input signal for
pulse output 0, which is used in the
origin search. To use this signal,
write the input from the actual sensor
as an input condition in the ladder
program and output the result to this
flag.
---
---
Cleared
---
---
Addresses
Name
Function
Settings
Status
after
mode
change
Status at
startup
Write
timing
Related
Flags,
Settings
Word
Bits
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...
Page 667: ...636 Revision History...