332
Serial Communications
Section 6-1
6-1
Serial Communications
6-1-1
Overview
The CP1H CPU Units support the following serial communications functions.
Protocol
Connected devices
Description
Serial
port 1
Serial
port 2
No-protocol
Standard devices supporting serial communications
Communicates with standard
devices with an RS-232C or
RS-422A/485 port without a
command–response format.
Instead the TXD(236) and
RXD(235) instructions are exe-
cuted from the program to
transmit data from the trans-
mission port or read data in the
reception port. The frame
headers and end codes can be
specified.
OK
OK
Serial gate-
way (to
CompoWay/
F or Mod-
bus-RTU)
OMRON components supporting CompoWay/F or Mod-
bus-RTU slave devices
Converts received FINS com-
mands into CompoWay/F or
Modbus-RTU commands and
transfers them on the serial
communications path.
OK
OK
Serial PLC
Link
CP1H or CJ1M CPU Units
Up to ten words per Unit can
be shared by up to nine CPU
Units, including one Polling
Unit and eight Polled Units.
An RS-422A/485 Option
Boards (CP1W-CIF11) are
used to communicate via RS-
422A/485, or RS-232C Option
Boards (CP1W-CIF01) can be
used to communicate between
two CPU Units via an RS-232C
connection.
CJ1M CPU Units can also be
included in Serial PLC Links,
and the Serial PLC Links can
also include PTs as Polled
Units via 1:N NT Links.
Note Serial PLC Links can be
created on serial port 1
or serial port 2, but not
on both ports at the
same time.
OK
OK
CP1H CPU Unit
Standard device with
serial communications
RS-232C or RS-422A/485
CP1H CPU Unit
RS-485 (CompoWay/F or Modbus-RTU)
OMRON CompoWay/F-compliant components
or Modbus-RUT slave devices
CP1H CPU Unit
Polling Unit
RS-422A/485 Option Board
RS-422A/485
Shared data
CP1H CPU Unit
Polled Unit
CP1H CPU Unit
Polled Unit
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...