Installation Precautions
Section 3-2
3-2
Installation Precautions
3-2-1
Installation and Wiring Precautions
Always consider the following factors when installing and wiring the PLC to
improve the reliability of the system and make the most of the CP1H func-
tions.
Ambient Conditions
Do not install the PLC in any of the following locations.
• Locations subject to ambient temperatures lower than 0
°
C or higher than
55
°
C.
• Locations subject to drastic temperature changes or condensation.
• Locations subject to ambient humidity lower than 10% or higher than
90%.
• Locations subject to corrosive or flammable gases.
• Locations subject to excessive dust, salt, or metal filings.
• Locations that would subject the PLC to direct shock or vibration.
• Locations exposed to direct sunlight.
• Locations that would subject the PLC to water, oil, or chemical reagents.
Always enclose or protect the PLC sufficiently in the following locations.
• Locations subject to static electricity or other forms of noise.
• Locations subject to strong electromagnetic fields.
• Locations subject to possible exposure to radioactivity.
• Locations close to power lines.
Installation in
Cabinets or Control
Panels
When the CP1H is being installed in a cabinet or control panel, always provide
proper ambient conditions as well as access for operation and maintenance.
Temperature Control
The ambient temperature within the enclosure must be within the operating
range of 0
°
C to 55
°
C. When necessary, take the following steps to maintain
the proper temperature.
• Provide enough space for good air flow.
• Do not install the PLC above equipment that generates a large amount of
heat, such as heaters, transformers, or high-capacity resistors.
• If the ambient temperature exceeds 55
°
C, install a cooling fan or air con-
ditioner.
SYSMAC
CP1H
Control
panel
Fan
Louver
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...
Page 667: ...636 Revision History...