![background image](http://html1.mh-extra.com/html/omron/cp1h-cpu-05-2006/cp1h-cpu-05-2006_operation-manual_742082452.webp)
421
Analog I/O Units
Section 7-4
Creating a Ladder
Program
I/O Allocation
Two input words and one output word are allocated to the Analog I/O Unit
starting from the next word following the last allocated word on the CPU Unit
or previous Expansion Unit or Expansion I/O Unit.
Writing the Range Code
Write the range code to word n+1. A/D or D/A conversion begins when the
range code is transferred from the CPU Unit to the Analog I/O Unit. There are
five range codes, 000 to 100, that combine the analog input 1 and 2 and ana-
log output signal ranges, as shown below.
Example
The following instructions set analog input 0 to 4 to 20 mA, analog input 1 to 0
to 10 V, and the analog output to
−
10 to 10 V.
• The Analog I/O Unit will not start converting analog I/O values until the
range code has been written. Until conversion starts, inputs will be 0000,
and 0 V or 0 mA will be output.
• After the range code has been set, 0 V or 0 mA will be output for the 0 to
10-V,
−
10 to 10-V, or 0 to 20-mA ranges, and 1 V or 4 mA will be output for
the 1 to 5-V and 4 to 20-mA ranges until a convertible value has been
written to the output word.
• Once the range code has been set, it is not possible to change the setting
while power is being supplied to the CPU Unit. To change the I/O range,
turn the CPU Unit OFF then ON again.
Range
code
Analog input 0 signal
range
Analog input 1 signal
range
Analog output signal
range
000
−
10 to 10 V
−
10 to 10 V
−
10 to 10 V
001
0 to 10 V
0 to 10 V
0 to 10 V
010
1 to 5 V/4 to 20 mA
1 to 5 V/4 to 20 mA
1 to 5 V
011
0 to 5 V/0 to 20 mA
0 to 5 V/0 to 20 mA
0 to 20 mA
100
---
---
4 to 20 mA
Analog I/O Unit
Word m+1
Word m+2
32 inputs
16 outputs
Word n+1
n+1
15
1 0 0
0
0
0
0
8 7 6 5
4
3
2
1
0
Analog
output
Analog
input 1
Analog
input 0
MOV(021)
#800A
n+1
First Cycle Flag
A200.11
Analog input 0: 4 to 20 mA
Analog input 1: 0 to 10 V
Analog output:
−
10 to 10 V
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...
Page 667: ...636 Revision History...