253
Pulse Outputs
Section 5-3
Note An origin search will not be started unless the origin search proximity speed is
less than the origin search high speed and unless the origin search/return ini-
tial speed is less than the origin search proximity speed.
Explanation of the Origin Search Parameters
Operating Mode
The operating mode parameter specifies the kind of I/O signals that are used
in the origin search. The 3 operating modes indicate whether the Error
Counter Reset Output and Positioning Completed Input are used.
Origin compensation
80000000 to 7FFFFFFF hex
(
−
2147483648 to 2147483647)
Start of
operation
I/O settings
Limit Input Signal type
0: Normally closed (NC)
1: Normally open (NO)
Start of
operation
Origin Proximity Input Signal type
0: Normally closed (NC)
1: Normally open (NO)
Start of
operation
Origin Input Signal type
X/XA CPU Units
0: Normally closed (NC)
1: Normally open (NO)
Y CPU Units (Pulse outputs 0 and 1)
0: Normally closed (NC) (Open collector)
1: Normally open (NO) (Open collector)
2: Normally closed (NC) (Line driver)
3: Normally open (NO) (Line driver)
Y CPU Units (Pulse outputs 2 and 3)
0: Normally closed (NC)
1: Normally open (NO)
When power
is turned ON
Positioning monitor time
0000 to 270F hex
(0 to 9,999 ms)
Start of
operation
Name
Settings
Time when
read
Operating
mode
I/O signal
Remarks
Origin Input
Signal
Error Counter
Reset Output
Positioning Completed
Input
Operation when the origin is
detected during deceleration from
the origin search's high speed
0
The origin position
is determined
when the Origin
Input Signal goes
from OFF to ON.
Not used.
The origin search
operation ends
after the origin is
detected.
Not used.
The Origin Input Signal will be
detected during deceleration. An Ori-
gin Input Signal Error (error code
0202) will occur and the motor will
decelerate to a stop.
1
Goes ON for 20 to
30 ms when the
origin is detected.
The Origin Input Signal will not be
detected during deceleration. When
the Origin Input Signal is detected
after the motor has reached the prox-
imity speed for origin search, the
motor will be stopped and the origin
search operation will end.
2
After the origin is
detected, the origin
search will not be end
until the Positioning
Completed Input is
received from the driver.
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...
Page 667: ...636 Revision History...