![background image](http://html1.mh-extra.com/html/omron/cp1h-cpu-05-2006/cp1h-cpu-05-2006_operation-manual_742082106.webp)
75
CP1H CPU Unit Operation
Section 2-3
Routing Tables
Tables specifying the communications paths from the Communications Units
on the local PLC to remote PLCs connected on other networks must be regis-
tered in all the CPU Units in network PLCs to send and receive data between
networks. These tables are called the routing tables. The routing tables con-
sist of the relay network table and local network table.
Routing tables are created from the CX-Programmer or Support Software for
Communications Units (e.g., CX-Integrator) and then transferred to each CPU
Unit.
Remote Network Table
The remote network tables lists the node number and network address of the
first relay node that must be passed through to reach any remote network to
which the PLC is not directly connected. Once the routing tables have been
registered, any remote network can be reached by passing through relay
nodes.
Local Network Table
The local network table contains the unit number and network address of all
Communications Units that are part of the local PLC.
CPU Bus Unit Setup Area
The CPU Bus Unit Setup Area contains the system settings for CPU Bus Unit
controlled by the CPU Unit. The specific settings that are available depend on
the CPU Bus Unit that is being used. Refer to the operation manual for the
CPU Bus Unit for details.
This area cannot be directly accessed by the user in the same way as I/O
memory. All settings are made from the CX-Programmer. Refer to the CX-Pro-
grammer Operation Manual for setting procedures.
3
N
3
M
PLC 1
PLC 2
PLC 3
PLC 4
3
1
2
n
Node M
Unit number n
Network 1
Network 2
Network 3
Node N
Relay Network Table for PLC 1
Relay Network Table for PLC 2
Local Network Table for PLC 3
Remote
network
Relay
network
Relay
node
Remote
network
Relay
network
Relay
node
Local
network
Unit
number
CX-Programmer
CPU Bus Unit
CPU Unit
CPU Bus
Unit Setup
Area
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...
Page 667: ...636 Revision History...