326
Analog I/O (XA CPU Units)
Section 5-5
1. Setting the Analog Voltage/Current Input Switches
Each analog input can be set for use as a voltage input or current input.
Each input’s input range is set independently in the PLC Setup. The voltage
input range can be set to 0 to 5 V, 1 to 5 V, 0 to 10 V, or
−
10 to 10 V. The cur-
rent input range can be set to 0 to 20 mA or 4 to 20 mA.
Note
The built-in analog input switch is located on the PCB inside the case. To
make setting the switch easier, make the switch settings before mounting the
terminal block to the base.
When setting this switch, be very careful not to damage the wiring on the
PCB.
2. PLC Setup
Use the CX-Programmer to set the various PLC Setup including whether the I/
O point is being used, the input range, output range, averaging function
usage, and resolution. The I/O point usage, input range, output range, and
averaging function usage can be set independently for each I/O point, but the
resolution setting applies to all of the I/O points.
• The input range can be set to
−
10 to 10 V, 0 to 10 V, 1 to 5 V, 0 to 5 V, 0 to
20 mA or 4 to 20 mA.
• The output range can be set to
−
10 to 10 V, 0 to 10 V, 1 to 5 V, 0 to 5 V, 0
to 20 mA or 4 to 20 mA.
• Once the range has been set, it cannot be changed as long as the CP1H
CPU Unit’s power is ON. To change the input range or output range,
change the setting in the PLC Setup, turn the CPU Unit OFF, and then
turn the CPU Unit ON again.
ON
1
2
3
4
ON
OFF
Analog input 4 selection switch
Analog input 3 selection switch
Analog input 2 selection switch
Analog input 1 selection switch
OFF: Voltage input (factory default setting)
ON: Current input
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...
Page 667: ...636 Revision History...