549
Auxiliary Area Allocations by Address
Appendix D
A402
A402.06 Special I/O
Unit Error Flag
(non-fatal
error)
ON when an error occurs in a data
exchange between the CPU Unit and
a Special I/O Unit (including an error
in the Special I/O Unit itself).
The CPU Unit will continue operating
and the ERR/ALM indicator on the
front of the CPU Unit will flash. The
Special I/O Unit where the error
occurred will stop operating and the
unit number of the Unit where the
data exchange error occurred is indi-
cated in A418 through A423.
(This flag will be turned OFF when
the error is cleared.)
ON: Error in
one or more
Units
OFF: No
errors in any
Unit
Cleared
Cleared
Refreshed
when error
occurs.
A418 to
A423
A402.07 CPU Bus Unit
Error Flag
(non-fatal
error)
ON when an error occurs in a data
exchange between the CPU Unit and
an CPU Bus Unit (including an error
in the CPU Bus Unit itself).
The CPU Unit will continue operating
and the ERR/ALM indicator on the
front of the CPU Unit will flash. The
CPU Bus Unit where the error
occurred will stop operating and the
unit number of the Unit where the
data exchange error occurred is indi-
cated in A417.
(This flag will be turned OFF when
the error is cleared.)
ON: Error in
one or more
Units
OFF: No error
in any Unit
Cleared
Cleared
Refreshed
when error
occurs.
A417
A402.10 PLC Setup
Error Flag
(non-fatal
error)
ON when there is a setting error in
the PLC Setup. The CPU Unit will
continue operating and the ERR/
ALM indicator on the front of the
CPU Unit will flash. The location of
the error will be written to A406.
(This flag will be turned OFF when
the error is cleared.)
ON: Error
OFF: No error
Cleared
Cleared
Refreshed
when error
occurs.
A406
A402.13 Interrupt Task
Error Flag
(non-fatal
error)
ON when the Detect Interrupt Task
Errors setting in the PLC Setup is set
to “Detect” and an interrupt task is
executed for more than 10 ms during
I/O refreshing of a Special I/O Unit.
This flag will also be turned ON if an
attempt is made to refresh a Special
I/O Unit’s I/O from an interrupt task
with IORF(097) while the Unit’s I/O is
being refreshed by cyclic I/O refresh-
ing (duplicate refreshing).
The CPU Unit will continue operating
and the ERR/ALM indicator on the
front of the CPU Unit will flash.
(This flag will be turned OFF when
the error is cleared.)
ON: Interrupt
task error
OFF: No error
Cleared
Cleared
Refreshed
when error
occurs.
A426,
PLC
Setup
(Detect
Interrupt
Task
Errors set-
ting)
A402.15 FAL Error Flag
(non-fatal
error)
ON when a non-fatal error is gener-
ated by executing FAL(006). The
CPU Unit will continue operating and
the ERR/ALM indicator on the front
of the CPU Unit will flash.
The bit in A360 to A391 that corre-
sponds to the FAL number specified
in FALS(006) will be turned ON and
the corresponding error code will be
written to A400. Error codes 4101 to
42FF correspond to FAL numbers
001 to 2FF (0 to 511).
(This flag will be turned OFF when
the error is cleared.)
ON:
FALS(006)
error occurred
OFF:
FALS(006)
not executed
Cleared
Cleared
Refreshed
when error
occurs.
A360 to
A391,
A400
Address
Name
Function
Settings
Status
after
mode
change
Status
at star-
tup
Write
timing
Related
flags, set-
tings
Words
Bits
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...
Page 667: ...636 Revision History...