87
CPU Unit Operating Modes
Section 2-5
2-5-3
Operating Mode Changes and I/O Memory
Operating Mode Changes and I/O Memory
Note
1.
The following processing is performed if the I/O Memory Hold Bit is ON.
Outputs from Output Units will be turned OFF when operation stops even
if I/O bit status is held in the CPU Unit.
2.
The cycle time will increase by approximately 10 ms when the operating
mode is changed from MONITOR to RUN mode. This will not, however,
cause an error for exceeding the maximum cycle time limit.
Note Refer to SECTION 4 I/O Memory Allocation.
2-5-4
Startup Mode Setting
This setting in the PLC Setup determines the operating mode that will be used
by the CPU Unit when the power supply is turned ON.
PLC Setup
Mode Changes
Non-holding areas
Holding Areas
• I/O bits
• Data Link bits
• CPU Bus Unit bits
• Special I/O Unit bits
• Work bits
• Timer PV/Completion Flags
• Index Registers
• Data Registers
• Task Flags
Auxiliary Area bits/words are holding or
non-holding depending on the address.
• HR Area
• DM Area
• Counter PV and Completion Flags
Auxiliary Area bits/words are holding or
non-holding depending on the address.
RUN or MONITOR to PROGRAM Cleared (See note 1.)
Held
PROGRAM to RUN or MONITOR Cleared (See note 1.)
Held
RUN to MONITOR or
MONITOR to RUN
Held (See note 2.)
Held
I/O Memory
Hold Bit status
(A500.12)
I/O Memory
Output bits allocated to Output Units
Mode changed
between
PROGRAM
and RUN/
MONITOR
Operation stopped
Mode changed
between
PROGRAM
and RUN/
MONITOR
Operation stopped
Fatal error
other than
FALS
FALS
executed
Fatal error
other than
FALS
FALS
executed
OFF
Cleared
Cleared
Held
OFF
OFF
OFF
ON
Held
Held
Held
Held
OFF
OFF
Power turned ON.
Operating mode
Name
Description
Settings
Default
Startup Mode
Specifies the
CPU Unit oper-
ating mode at
startup
• Program
• Monitor
• Run
• Use programming console
Use program-
ming console
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...
Page 667: ...636 Revision History...