114
Mounting
Section 3-3
• Slide the yellow sliders at the top and bottom of each Unit to lock the
Units together.
Note
If the sliders are not secured properly, the Unit may not function properly.
3.
Attach the End Cover to the Unit on the far right side of the Rack.
Note
Attach the End Cover to the Unit on the far right side of the Rack. An I/O bus
error will occur and CP1H CPU Unit will not operate in either RUN or MONI-
TOR mode if the End Cover is not connected. If this occurs, the following infor-
mation will be set in memory.
• Always turn OFF the power supply before connecting Units to each
other.
3-3-4
DIN Track Installation
1,2,3...
1.
Use a screwdriver to pull down the DIN Track mounting pins from the back
of the Units, and mount the Units to the DIN Track.
Move the sliders toward the
back until they lock into place.
Lock
Release
Slider
Name
Address
Status
I/O Bus Error Flag
A401.14
ON
I/O Bus Error Details
A404
0E0E hex
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...
Page 667: ...636 Revision History...