567
Auxiliary Area Allocations by Address
Appendix D
Error Codes and Error Flags
Note 1.
C101 to C2FF will be stored for FALS numbers 001 to 511.
2.
4101 to 42FF will be stored for FAL numbers 001 to 511.
3.
The contents of the error flags for a duplicate number error are as follows:
Bits 00 to 07: Unit number (binary), 00 to 5F hex for Special I/O Units, 00 to 0F hex for CPU Bus Units
Bits 08 to 14: All zeros.
Bit 15: Unit type, 0 for CPU Bus Units and 1 for Special I/O Units.
4.
Only the contents of A295 is stored as the error flag contents for program errors.
5.
A value of 0000 hex will be stored as the error flag contents.
A200.11: First Cycle Flag
A200.15: Initial Task Flag
A200.15 will turn ON during the first time a task is executed after it has reached executable status. It will be ON
only while the task is being executed and will not turn ON if following cycles.
Classification
Error code
Meaning
Error flags
System-defined
fatal errors
80F1
Memory error
A403
80C0 to 80C7
80CE, 80CF
I/O bus error
A404
80E9
Duplicate number error
A410, A411 to 416 (See note 3.)
80E1
Too many I/O error
A407
80E0
I/O setting error
---
80F0
Program error
A295 to A299 (See note 4.)
809F
Cycle time too long error
---
80EA
Duplicate Expansion Rack number error
A409.00 to A409.07
User-defined
fatal errors
C101 to C2FF
FALS instruction executed (See note 1.)
---
User-defined
non-fatal errors
4101 to 42FF
FAL instruction executed (See note 2.)
---
System-defined
non-fatal errors
008B
Interrupt task error
A426
009A
Basic I/O error
A408
009B
PLC Setup setting error
A406
0200 to 020F
CPU Bus Unit error
A417
0300 to 035F
Special I/O Unit error
A418 to A423 (See note 5.)
00F7
Battery error
---
0400 to 040F
CPU Bus Unit setup error
A427
0500 to 055F
Special I/O Unit setup error
A428 to A433 (See note 5.)
Time
1 cycle
Execution
started.
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...
Page 667: ...636 Revision History...