432
Temperature Sensor Units
Section 7-5
Programming with BCD(24) Instruction
002
#7FFF
1000.00
CMP(020)
1000.00
2
#7FFE
Always ON
P_On
CMP(020)
Detects completion of input 0 initialization.
P_EQ
1000.01
2
D0
BCD(024)
2.15
#0000
2
SBB(051)
P_EQ
2.15
#0000
D1
MOV(021)
CLC(041)
D0
D0
D0
BCD(024)
#0001
D1
MOV(021)
Execution
condition
ON when input 0 has been initialized
Detects an open-circuit alarm or Unit
error by checking whether the error code
7FFF has been output
ON when an open-circuit alarm or Unit
error has been detected for input 0.
Stores positive BCD data in D00000.
Stores #0000 in D00001.
When input 0 converted value is negative
(#0000 minus two's complement = actual
value)
Stores negative BCD data in D0.
Stores #0001 in D1 to indicate a
negative number.
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...
Page 667: ...636 Revision History...