475
Troubleshooting
Section 9-2
Special I/O Unit Errors
■
Reference Information
Option Board Errors
■
Reference Information
Battery Error
■
Reference Information
Seven-segment display
Probable cause and possible remedy
0.3.
→
0.0.
→
Special I/O Unit
error, unit num-
ber 0
A data exchange error has occurred between the
CPU Unit and one of the Special I/O Units.
Note Information on where the data exchange error
occurred (i.e., between the CPU Unit and what
Unit number) is stored in A418 to A423. Check
the Unit given in A418 to A423.
Refer to the manual for the relevant Unit and remove
the cause of the error. Then turn ON the Restart Bit
or cycle the power supply.
Replace the Unit if operation is not restored when the
Unit is restarted.
0.3.
→
s.f.
→
Special I/O Unit
error, unit num-
ber 95
0.3.
→
f.f.
→
Special I/O Unit
error, unit num-
ber unknown
Error flag
Special I/O Unit Error Flag, A402.06
Error code (A400)
0300 to 035F, 03FF
Error information
Special I/O Unit Error Unit Number Flags, A418 to A423
Seven-segment display
Probable cause and possible remedy
0.0.
→
d.1.
→
Option Board error
(option slot 1)
A315.13 will turn ON if the Option Board is
removed while the power is being supplied.
Turn OFF the power supply and then install the
Option Board again.
0.0.
→
d.2.
→
Option Board error
(option slot 2)
Error flags
Option Board Error Flag, A315.13
Other Non-fatal Error Flag, A402.00
Error code (A400)
---
Error information
---
Seven-segment
display
Probable cause and possible remedy
0.0.
→
f.7.
→
If the PLC Setup is set to detect battery errors, this error will occur
when there is an error in the battery in the CPU Unit (i.e., the volt-
age is low or a battery is not mounted). Check the battery connec-
tions.
When using battery-free operation, disable connecting battery
errors in the PLC Setup.
Error flag
Battery Error Flag, A402.04
Error code (A400)
00F7
Error information
---
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...
Page 667: ...636 Revision History...