0 to 20 mA Inputs
When the resolution is set to 1/6,000, the 0 to 20-mA range corresponds to
hexadecimal values 0000 to 1770 (0 to 6,000). The entire data range is FED4
to 189C (
−
300 to 6,300).
When the resolution is set to 1/12,000, the 0 to 20-mA range corresponds to
hexadecimal values 0000 to 2EE0 (0 to 12,000). The entire data range is
FDA8 to 3138 (
−
600 to 12,600).
A negative voltage is expressed as a two’s complement.
The following diagram shows conversion values for 1/6,000 resolution.
4 to 20 mA
When the resolution is set to 1/6,000, the 4- to 20-mA range corresponds to
hexadecimal values 0000 to 1770 (0 to 6,000). The entire data range is FED4
to 189C (
−
300 to 6,300).
When the resolution is set to 1/12,000, the 4- to 20-mA range corresponds to
hexadecimal values 0000 to 2EE0 (0 to 12,000). The entire data range is
FDA8 to 3138 (
−
600 to 12,600).
Inputs between 3.2 and 4 mA are expressed as two’s complements. If the
input falls below 3.2 mA, open-circuit detection will activate and converted
data will be 8000.
1 V
5 V 5.2 V
0.8 V
FED4 (
−
300)
189C (6300)
1770 (6000)
0000 (0)
Converted Data
Hexadecimal (Decimal)
0 mA
20 mA 21 mA
−
1 mA
FED4 (
−
300)
189C (6300)
1770 (6000)
0000 (0)
Converted Data
Hexadecimal (Decimal)
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...
Page 667: ...636 Revision History...