608
PLC Setup
Appendix G
2
2-2
NT Link (1:N)
2-2-1
Baud
9,600
(disabled)
38,400 (standard)
Every cycle
161
00 to
07
00 hex
115,200 (high speed)
0A hex
2-2-2
NT/PC
Link Max:
Highest
unit num-
ber
0
0
Every cycle
166
00 to
03
0 hex
:
:
7
7 hex
2-3
RS-232C
2-3-1
Baud
9600 bps
300 bps
Every cycle
161
00 to
07
01 hex
600 bps
02 hex
1,200 bps
03 hex
2,400 bps
04 hex
4,800 bps
05 hex
9,600 bps
00 or
06 hex
19,200 bps
07 hex
38,400 bps
08 hex
57,600 bps
09 hex
115,200 bps
0A hex
2-3-2
Format
(data
length,
stop bits,
parity)
7,2,E: 7-bit
data, 2 stop
bits, even parity
7,2,E: 7-bit data, 2 stop
bits, even parity
Every cycle
160
00 to
03
0 hex
7,2,O: 7-bit data, 2 stop
bits, odd parity
1 hex
7,2,N: 7-bit data, 2 stop
bits, no parity
2 hex
7,1,E: 7-bit data, 2 stop
bits, even parity
4 hex
7,1,O: 7-bit data, 1 stop
bit, odd parity
5 hex
7,1,N: 7-bit data, 1 stop
bit, no parity
6 hex
8,2,E: 8-bit data, 2 stop
bits, even parity
8 hex
8,2,O: 8-bit data, 2 stop
bits, odd parity
9 hex
8,2,N: 8-bit data, 2 stop
bits, no parity
A hex
8,1,E: 8-bit data, 1 stop
bit, even parity
C hex
8,1,O: 8-bit data, 1 stop
bit, odd parity
D hex
8,1,N: 8-bit data, 1 stop
bit, no parity
E hex
2-3-3
Start Code Disable.
Disable.
Every cycle
165
12
0
Set. 1
2-3-4
Start Code 00 hex0x0000
0x0000
Every cycle
164
08 to
15
00 hex
:
:
0x00FF
FF hex
2-3-5
End Code
Received
Bytes: Receive
specified num-
ber of bytes.
Received Bytes: Receive
specified number of
bytes.
Every cycle
165
08 and
09
00
CR,LF
10
Set End Code
01
2-3-6
Received
Bytes
256 bytes
256 bytes
Every cycle
165
00 to
07
00 hex
1 byte
01 hex
:
:
255 bytes
FF hex
Name
Default
Settings
When setting is read
by CPU Unit
Internal
address
Bits
Settings
Summary of Contents for CP1H-CPU - 05-2006
Page 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Page 3: ...iv...
Page 11: ...xii TABLE OF CONTENTS...
Page 15: ...xvi...
Page 19: ...xx...
Page 31: ...xxxii Conformance to EC Directives 6...
Page 71: ...40 Function Blocks Section 1 5...
Page 133: ...102 Computing the Cycle Time Section 2 7...
Page 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Page 411: ...380 Clock Section 6 8...
Page 519: ...488 Replacing User serviceable Parts Section 10 2...
Page 527: ...496 Standard Models Appendix A...
Page 535: ...504 Dimensions Diagrams Appendix B...
Page 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Page 659: ...628 PLC Setup Appendix G...
Page 665: ...634 Index work words 159 write protection 370...