APPENDIX
App. - 10
App. 4.3 Mounting/dismounting
Installation direction and clearances
CAUTION
The devices must be installed in the specified direction. Not doing so may cause
a malfunction.
Mount the servo amplifier on a cabinet which meets IP54 in the correct vertical
direction to maintain pollution degree 2.
Note the followings for supplied regenerative resistors of 11 kW to 22 kW servo
amplifiers because they do not have protect covers.
Touching the resistor will cause a burn because the surface of the parts is a
resistive element and very high temperature.
Even if the power turned off, touching the resistor will cause an electric shock
because the capacitor of the servo amplifier is charged for a while.
10 mm or
more
80 mm or longer
for wiring
10 mm or
more
(Note 2)
Top
Bottom
40 mm or
more
(Note 1)
40 mm or
more
Cabinet
Servo amplifier
Servo amplifier
Cabinet
Note 1. For 11 kW to 22 kW servo amplifiers, the clearance between the bottom and
ground will be 120 mm or more.
2. For MR-J4-500_, the clearance on the left side will be 25 mm or more.
To adapt your machine using MR-J4-03A6 or MR-J4W2-0303B6 to IEC/EN 60950-1, either supply the
amplifier with a power supply complying with the requirement of 2.5 stated in IEC/EN 60950-1 (Limited
Power Source), or cover the amplifier and motors connected to the outputs with a fire enclosure.
Summary of Contents for MR-J4
Page 9: ...A 8 MEMO ...
Page 19: ...10 MEMO ...
Page 73: ...1 FUNCTIONS AND CONFIGURATION 1 54 MEMO ...
Page 155: ...3 SIGNALS AND WIRING 3 76 MEMO ...
Page 199: ...4 STARTUP 4 44 MEMO ...
Page 289: ...6 NORMAL GAIN ADJUSTMENT 6 24 MEMO ...
Page 335: ...8 TROUBLESHOOTING 8 8 MEMO ...
Page 357: ...9 OUTLINE DRAWINGS 9 22 MEMO ...
Page 517: ...12 ABSOLUTE POSITION DETECTION SYSTEM 12 30 MEMO ...
Page 617: ...16 USING A DIRECT DRIVE MOTOR 16 20 MEMO ...
Page 641: ...17 FULLY CLOSED LOOP SYSTEM 17 24 MEMO ...
Page 725: ...18 MR J4 03A6 SERVO AMPLIFIER 18 84 MEMO ...
Page 763: ...APPENDIX App 38 ...
Page 789: ...MEMO ...
Page 793: ......