12. ABSOLUTE POSITION DETECTION SYSTEM
12 - 21
(2) Data set type home position return
POINT
Never make home position setting during command operation or servo motor
rotation. It may cause home position sift.
It is possible to execute data set type home position return during the servo off.
Move the machine to the position where the home position is to be set by performing manual operation
such as JOG operation. When CR is on for longer than 20 ms, the stop position is stored into the non-
volatile memory as the home position absolute position data.
When the servo on, set CR to on after confirming that INP is on. If this condition is not satisfied, [AL. 96
Home position setting warning] will occur, but that warning will be reset automatically by making home
position return correctly.
The number of home position setting times is limited to 100,000 times.
OFF
ON
INP (In-position)
OFF
ON
CR (Home position setting)
ABSB0 (ABS transmission data bit 0)
ABSB1 (ABS transmission data bit 1)
Servo motor
Update
20 ms or longer
Manual feed (JOG, etc.)
OFF
ON
OFF
ON
ABSV
(Absolute position undetermined)
Control circuit power supply
Summary of Contents for MR-J4
Page 9: ...A 8 MEMO ...
Page 19: ...10 MEMO ...
Page 73: ...1 FUNCTIONS AND CONFIGURATION 1 54 MEMO ...
Page 155: ...3 SIGNALS AND WIRING 3 76 MEMO ...
Page 199: ...4 STARTUP 4 44 MEMO ...
Page 289: ...6 NORMAL GAIN ADJUSTMENT 6 24 MEMO ...
Page 335: ...8 TROUBLESHOOTING 8 8 MEMO ...
Page 357: ...9 OUTLINE DRAWINGS 9 22 MEMO ...
Page 517: ...12 ABSOLUTE POSITION DETECTION SYSTEM 12 30 MEMO ...
Page 617: ...16 USING A DIRECT DRIVE MOTOR 16 20 MEMO ...
Page 641: ...17 FULLY CLOSED LOOP SYSTEM 17 24 MEMO ...
Page 725: ...18 MR J4 03A6 SERVO AMPLIFIER 18 84 MEMO ...
Page 763: ...APPENDIX App 38 ...
Page 789: ...MEMO ...
Page 793: ......