11. OPTIONS AND AUXILIARY EQUIPMENT
11 - 43
11.5.2 Selection example
(1) 200 V class
FR-CV power regeneration common converter can be used for the 200 V class servo amplifier of 100 W
to 22 kW. The following shows the restrictions on using the FR-CV.
(a) Up to six servo amplifiers can be connected to one FR-CV.
(b) FR-CV capacity [W]
≥
Total of rated capacities [W] × 2 of servo amplifiers connected to FR-CV.
(c) The total of used servo motor rated currents should be equal to or less than the applicable current
[A] of the FR-CV.
(d) Among the servo amplifiers connected to the FR-CV, the servo amplifier of the maximum capacity
should be equal to or less than the maximum connectable capacity [W].
The following table lists the restrictions.
Item
FR-CV-_
7.5K 11K 15K 22K 30K 37K 55K
Maximum number of connected servo
amplifiers
6
Total of connectable servo amplifier
capacities [kW]
3.75 5.5 7.5 11 15 18.5 27.5
Total of connectable servo motor rated
currents [A]
33 46 61 90 115
145
215
Maximum servo amplifier capacity [kW]
3.5
5
7
11
15
15
22
When using the FR-CV, always install the dedicated stand-alone reactor (FR-CVL).
Power regeneration common
converter
Dedicated stand-alone
reactor
FR-CV-7.5K(-AT) FR-CVL-7.5K
FR-CV-11K(-AT) FR-CVL-11K
FR-CV-15K(-AT) FR-CVL-15K
FR-CV-22K(-AT) FR-CVL-22K
FR-CV-30K(-AT) FR-CVL-30K
FR-CV-37K FR-CVL-37K
FR-CV-55K FR-CVL-55K
Summary of Contents for MR-J4
Page 9: ...A 8 MEMO ...
Page 19: ...10 MEMO ...
Page 73: ...1 FUNCTIONS AND CONFIGURATION 1 54 MEMO ...
Page 155: ...3 SIGNALS AND WIRING 3 76 MEMO ...
Page 199: ...4 STARTUP 4 44 MEMO ...
Page 289: ...6 NORMAL GAIN ADJUSTMENT 6 24 MEMO ...
Page 335: ...8 TROUBLESHOOTING 8 8 MEMO ...
Page 357: ...9 OUTLINE DRAWINGS 9 22 MEMO ...
Page 517: ...12 ABSOLUTE POSITION DETECTION SYSTEM 12 30 MEMO ...
Page 617: ...16 USING A DIRECT DRIVE MOTOR 16 20 MEMO ...
Page 641: ...17 FULLY CLOSED LOOP SYSTEM 17 24 MEMO ...
Page 725: ...18 MR J4 03A6 SERVO AMPLIFIER 18 84 MEMO ...
Page 763: ...APPENDIX App 38 ...
Page 789: ...MEMO ...
Page 793: ......