10. CHARACTERISTICS
10 - 13
10.5 Inrush currents at power-on of main circuit and control circuit
POINT
The inrush current values can change depending on frequency of turning on/off
the power and ambient temperature.
Since large inrush currents flow in the power supplies, always use molded-case circuit breakers and
magnetic contactors. (Refer to section 11.10.)
When circuit protectors are used, it is recommended that the inertia delay type, which is not tripped by an
inrush current, be used.
(1) 200 V class
The following shows the inrush currents (reference data) that will flow when 240 V AC is applied at the
power supply capacity of 2500 kVA and the wiring length of 1 m. When you use a 1-phase 200 V AC
power supply with MR-J4-10A(-RJ) to MR-J4-70A(-RJ), the inrush currents of the main circuit power
supply are the same.
Servo amplifier
Inrush currents (A
0-P
)
Main circuit power supply
(L1, L2 and L3)
Control circuit power supply
(L11 and L21)
MR-J4-10A(-RJ)
MR-J4-20A(-RJ)
MR-J4-40A(-RJ)
MR-J4-60A(-RJ)
30 A
(attenuated to approx. 3 A in 20 ms)
20 A to 30 A
(attenuated to approx. 1 A in 20 ms)
MR-J4-70A(-RJ)
MR-J4-100A(-RJ)
34 A
(attenuated to approx. 7 A in 20 ms)
MR-J4-200A(-RJ)
MR-J4-350A(-RJ)
113 A
(attenuated to approx. 12 A in 20 ms)
MR-J4-500A(-RJ)
42 A
(attenuated to approx. 20 A in 20 ms)
34 A
(attenuated to approx. 2 A in 20 ms)
MR-J4-700A(-RJ)
85 A
(attenuated to approx. 20 A in 30 ms)
MR-J4-11KA(-RJ)
226 A
(attenuated to approx. 30 A in 30 ms)
42 A
(attenuated to approx. 2 A in 30 ms)
MR-J4-15KA(-RJ)
226 A
(attenuated to approx. 50 A in 30 ms)
MR-J4-22KA(-RJ)
226 A
(attenuated to approx. 70 A in 30 ms)
Summary of Contents for MR-J4
Page 9: ...A 8 MEMO ...
Page 19: ...10 MEMO ...
Page 73: ...1 FUNCTIONS AND CONFIGURATION 1 54 MEMO ...
Page 155: ...3 SIGNALS AND WIRING 3 76 MEMO ...
Page 199: ...4 STARTUP 4 44 MEMO ...
Page 289: ...6 NORMAL GAIN ADJUSTMENT 6 24 MEMO ...
Page 335: ...8 TROUBLESHOOTING 8 8 MEMO ...
Page 357: ...9 OUTLINE DRAWINGS 9 22 MEMO ...
Page 517: ...12 ABSOLUTE POSITION DETECTION SYSTEM 12 30 MEMO ...
Page 617: ...16 USING A DIRECT DRIVE MOTOR 16 20 MEMO ...
Page 641: ...17 FULLY CLOSED LOOP SYSTEM 17 24 MEMO ...
Page 725: ...18 MR J4 03A6 SERVO AMPLIFIER 18 84 MEMO ...
Page 763: ...APPENDIX App 38 ...
Page 789: ...MEMO ...
Page 793: ......