17. FULLY CLOSED LOOP SYSTEM
17 - 11
(2) Selection of fully closed loop system
By setting [Pr. PA01], [Pr. PE01] and the control command of controller, the control method can be
selected as shown in the following table.
[Pr. PA01]
[Pr. PE01]
Semi closed loop
control/fully closed loop
control switching signal
Command unit
Control method
Absolute position
detection system
"_ _ 0 _"
Semi closed
loop system
(standard
control mode)
Servo motor
encoder unit
Semi closed loop control
"_ _ 1 _ "
Fully closed
loop system
(fully closed
loop control
mode)
"_ _ _ 0"
Load-side encoder
unit
Dual feedback control (fully
closed loop control)
(Note)
"_ _ _ 1"
Off
Semi closed loop control
×
On
Dual feedback control (fully
closed loop control)
×
Note. Applicable when the load-side encoder is set as the absolute position encoder.
(1) Operation mode selection
Select a operation mode.
Operation mode selection
[Pr. PA01]
1 0
0
Semi closed loop system
(Standard control mode)
Fully closed loop system
(Fully closed loop control mode)
Load-side encoder
resolution unit
Set value
0
1
Operation mode
Servo motor-side
resolution unit
Control unit
(b) Semi closed loop control/fully closed loop control selection
Select the semi closed loop control/fully closed loop control.
Fully closed loop control selection
0: Always enabled
1: Switching using the control command of controller
(switching between semi closed/fully closed)
0
0
Selection using the control
command of controller
OFF
ON
Semi closed loop control
Fully closed loop control
Control method
When the operation mode selection in [Pr. PA01] is set to "_ _ 1 _"
(fully closed loop system), this setting is enabled.
0
[Pr. PE01]
Summary of Contents for MR-J4
Page 9: ...A 8 MEMO ...
Page 19: ...10 MEMO ...
Page 73: ...1 FUNCTIONS AND CONFIGURATION 1 54 MEMO ...
Page 155: ...3 SIGNALS AND WIRING 3 76 MEMO ...
Page 199: ...4 STARTUP 4 44 MEMO ...
Page 289: ...6 NORMAL GAIN ADJUSTMENT 6 24 MEMO ...
Page 335: ...8 TROUBLESHOOTING 8 8 MEMO ...
Page 357: ...9 OUTLINE DRAWINGS 9 22 MEMO ...
Page 517: ...12 ABSOLUTE POSITION DETECTION SYSTEM 12 30 MEMO ...
Page 617: ...16 USING A DIRECT DRIVE MOTOR 16 20 MEMO ...
Page 641: ...17 FULLY CLOSED LOOP SYSTEM 17 24 MEMO ...
Page 725: ...18 MR J4 03A6 SERVO AMPLIFIER 18 84 MEMO ...
Page 763: ...APPENDIX App 38 ...
Page 789: ...MEMO ...
Page 793: ......