(4) Error Message
common
Name
Description
Indication
Available Inverters
Operation
panel
Parameter unit
FR-PU04 FR-PU07
Operation panel lock
Operation lock mode is set. Operation
other than
is invalid.
(HOLD)
—
{
{
{
{
Password locked
Password function is active. Display
and setting of parameter is restricted.
(LOCD)
—
—
—
—
{
Parameter
write error
Write
disable
error
1) You attempted to make parameter
setting when [
Pr. 77 Parameter write
selection
] has been set to disable
parameter write.
2) Frequency jump setting range
overlapped.
3) Adjustable 5 points V/F setting
overlapped
4) The PU and inverter cannot make
normal communication
(Er1)
—
{
{
{
{
Write error
during
operation
When parameter write was performed
during operation with [
Pr. 77
2] and
the STF (STR) is ON.
(Er2)
—
{
{
{
{
Calibration
error
Analog input bias and gain calibration
values are too close.
(Er3)
—
{
{
{
{
Mode
designation
error
You attempted to make parameter
setting in the NET operation mode
when [
Pr. 77
2].
(Er4)
—
{
{
{
{
Copy
operation
error
Parameter
read error
An error occurred in the EEPROM on
the operation panel side during
parameter copy reading.
(rE1)
—
{
{
{
{
Parameter
write error
1) You attempted to perform
parameter copy write during
operation.
2) An error occurred in the EEPROM
on the operation panel side during
parameter copy writing.
(rE2)
—
{
{
{
{
Parameter
verification
error
1) Data on the operation panel side
and inverter side are different.
2) An error occurred in the EEPROM
on the operation panel side during
parameter verification.
(rE3)
—
{
{
{
{
Model
error
1) A different model was used for
parameter write and verification
during parameter copy.
2) When parameter copy write is
stopped after parameter copy read
is stopped
(rE4)
—
{
{
{
{
Error
1) The RES signal is ON
2) The PU and inverter cannot make
normal communication (contact
fault of the connector)
3) This indication may appear at
turning ON the main circuit when
the control circuit power (terminal
R1/L11, S1/L21) and the main
circuit power (terminal R/L1, S/L2,
T/L3) are connected to separate
power.
(Err.)
—
{
{
{
{
A700
F700
E700
D700