464
PARAMETER
z
Function Diagnosis (H08 or 08)
A communication check can be made since the
query message sent is returned unchanged as a
response message (function of sub function code
H00).
Query message
Normal response (Response message)
• Query message setting
• Description of normal response
1) to 4) (including CRC check) of the normal
response are the same as those of the query
message. For broadcast communication, no
response is returned in reply to a query.
Therefore, the next query must be made when
the inverter processing time has elapsed after
the previous query.
1) Slave
Address
2) Function
3) Sub function
4) Date
CRC Check
(8bit)
H08
(8bit)
H00
(8bit)
H00
(8bit)
H
(8bit)
L
(8bit)
L
(8bit)
H
(8bit)
1) Slave
Address
2) Function
3) Sub function
4) Date
CRC Check
(8bit)
H08
(8bit)
H00
(8bit)
H00
(8bit)
H
(8bit)
L
(8bit)
L
(8bit)
H
(8bit)
Message
Setting Description
1) Slave address
Set the address to which a message will be sent. Broadcast communication
cannot be made (0 is invalid).
2) Function
Set H08.
3) Sub function
Set H0000.
4) Data
Any data can be set if it is 2 bytes long. The setting range is H0000 to HFFFF.