244
PARAMETER
2.6 Setting output voltage (V/F control)
2.6.1
V/F pattern and torque boost [Pr. 0, 3, 14, 19, 46, 47, 112
*
, 113
*
]
(common)
The inverter controls not only the output frequency but also
the output voltage. The relationship between the output
frequency and voltage is as follows.
(*[
Pr. 112
,
Pr. 113
] are not available for
.)
common
F700
E700
D700
[
Pr. 14
] allows the load pattern to be selected between a
linear ramp (for constant torque load) and a square
curve (for variable torque load) for the ratio of the output
voltage to the output frequency at not more than the
base frequency.
When the base frequency is reached, the output voltage
is maximum and is almost equal to the input power
supply voltage. At not less than the base frequency, the
output voltage is kept constant. [
Pr. 19
] allows the setting
of the output voltage at not less than the base
frequency. Note that the voltage output is less than the
power supply voltage.
When power supply voltage varies, the output voltage
varies according to the power supply voltage. When a
value other than 8888 and 9999 is set to [
Pr.19 Base
frequency voltage
], output voltage is limited to within the
set voltage.
Set the base frequency in [
Pr. 3
] .
Set the output voltage at the output frequency of 0 in [
Pr.
0 Torque boost
] to increase/decrease the motor starting
torque.
% indicated for the [
Pr. 0 Torque boost
], assumes that the
output voltage ( power supply voltage) of the base
frequency is 100%.
When the advanced magnetic flux vector control, Simple
magnetic flux vector control, Real sensorless vector
control, and vector control are selected, [
Pr. 0, Pr. 3, Pr.
14, Pr. 19, Pr. 46, Pr. 47, Pr. 112, Pr. 113
] are invalid.
[
Pr.
]
Name
Initial Value
Setting Range
Available Inverters
14 Load pattern selection
0
1
0 For constant torque load
{
{
{
1 For variable-torque load
{
{
{
2
For constant torque elevators
(at reverse rotation boost 0%)
{
—
{
3
For constant torque elevators
(at forward rotation boost 0%)
{
—
{
4
When the RT signal is ON
............For constant torque load
When the RT signal is OFF
............For constant torque elevators
(at reverse rotation boost 0%)
{
—
—
5
When the RT signal is ON
............For constant torque load
When the RT signal is OFF
............For constant torque elevators
(at forward rotation boost 0%)
{
—
—
3
V/F (base frequency)
60Hz
0 to 400Hz
{
{
{
47 Second V/F (base frequency)
9999
0 to 400Hz
,
9999
{
{
{
113 Third V/F (base frequency)
9999
0 to 400Hz
,
9999
{
—
—
19 Base frequency voltage
9999
0 to 1000V
,
8888
,
9999
{
{
{
0
Torque boost
0 to 30%
{
{
{
0.75K or less
1.5K to 3.7K
5.5K, 7.5K
11K to 55K
75K or more
6%
4%
3%
2%
1%
0.75K
1.5K to 3.7K
5.5K, 7.5K
11K to 37K
45K, 55K
75K or more
6%
4%
3%
2%
1.5%
1%
46 Second torque boost
9999
0 to 30%, 9999
{
{
{
112 Third torque boost
9999
0 to 30%, 9999
{
—
—
A700
F700
E700
D700
A700 E700 D700
F700
A700 E700 D700
F700