2.9.2
Torque limit level setting [Pr. 22, 406, 803, 810 to 817, 858, 865, 868, 874]
(A700)
This function limits the output torque to the predetermined
value during speed control under Real sensorless vector
control and vector control.
In [
Pr. 810 Torque limit input method selection
], you can select
whether to set the torque limit level using parameters ([
Pr.
22(Pr. 812 to 814)
]) or using analog input terminals (terminal
1, 4, terminal 6 (FR-A7AZ)).
Turning TL signal ON sets [
Pr. 815 Torque limit level 2
] as the
torque limit level.
In addition, you can set torque limit level for forward (power
driving/regeneration) and reverse (power driving/
regeneration) operation individually.
Under Real sensorless vector control, the lower limit of
torque limit level is set 30% if the value less than 30% is
input.
A700
[
Pr.
]
Name
Initial Value Setting Range
Description
22
Stall prevention operation level
(Torque limit level)
150/200%
*1
0 to 400%
Set the torque limit level in % on the assumption that the rated
torque is 100%.
*1
For the 3.7K or less, the value changes from 150% to 200%
when V/F control or Advanced magnetic flux vector control is
changed to Real sensorless vector control or vector control.
406
High resolution analog input
selection
9999
0, 2 to 6, 9999
When the setting value is "4", torque limit level can be
changed with a signal to terminal 6.
When the setting value is "2", regenerative torque limit level
can be changed with a signal to terminal 6.
803
Constant power range torque
characteristic selection
0
0
Constant motor output limit
Select the torque limit in the
constant power range by
torque limit setting.
1
Constant torque limit
810
Torque limit input method selection
0
0
Internal torque limit
(Torque limit by parameter setting)
1
External torque limit
(Torque limit by terminal 1, 4*)
811
Set resolution switchover
0
0
Speed setting and running
speed monitor increments
from the PU, RS-485
communication or
communication option.
Torque limit setting increments
[
Pr. 22
],
[
Pr. 812 to Pr. 817
]
1r/min
0.1%
1
0.1r/min
10
1r/min
0.01%
11
0.1r/min
812
Torque limit level (regeneration)
9999
0 to 400%
Set the torque limit level for forward rotation regeneration.
9999
[
Pr. 22
]/limit at the analog terminal value
813
Torque limit level (3rd quadrant)
9999
0 to 400%
Set the torque limit level for reverse rotation driving.
9999
[
Pr. 22
]/limit at the analog terminal value
814
Torque limit level (4th quadrant)
9999
0 to 400%
Set the torque limit level for reverse rotation regeneration.
9999
[
Pr. 22
]/limit at the analog terminal value
815
Torque limit level 2
9999
0 to 400%
When the torque limit selection (TL) signal is ON, the [
Pr. 815
]
value is a torque limit value regardless of [
Pr. 810
] .
9999
Torque limit set in [
Pr. 810
] is valid.
816
Acceleration torque limit level
9999
0 to 400%
Set the torque limit value during acceleration.
9999
Same torque limit as at constant speed
817
Deceleration torque limit level
9999
0 to 400%
Set the torque limit value during deceleration.
9999
Same torque limit as at constant speed
858
Terminal 4 function assignment
0
0, 4, 9999
When 4 is set, the torque limit can be changed with a signal to
terminal 4.
865
Low speed detection
1.5H
Z
0 to 400H
Z
The low speed detection signal (LS) is output when the output
frequency decreases below the setting.
868
Terminal 1 function assignment
0
0 to 6, 9999
When 4 is set, the torque limit can be changed with a signal to
terminal 1.
When 2 is set, the regenerative torque limit can be changed
with a signal to terminal 1.
874
OLT level setting
150%
0 to 200%
This function can make an inverter trip if the torque limit is
activated to stall the motor. Set the output level for a trip.
* When FR-A7AZ is installed, torque limit from terminal 6 is also available.