![Mitsubishi Electric FR-A700 Series Technical Manual Download Page 287](http://html.mh-extra.com/html/mitsubishi-electric/fr-a700-series/fr-a700-series_technical-manual_239199287.webp)
321
PARAMETER
2
P
ARAM
ETE
R
z
Terminal 1 functional calibration parameter
z
Terminal 4 functional calibration parameter
z
Terminal 6 (FR-A7AZ) functional calibration parameter
(1) The relationship between analog input terminal and calibration parameter
[
Pr.
868
]
Setting
Terminal Function
Calibration Parameters
Bias setting
Gain setting
0
(initial
value)
Frequency (speed) setting
auxiliary
[
C2(Pr. 902) Terminal 2 frequency setting bias frequency
]
[
C3(Pr. 902) Terminal 2 frequency setting bias
]
[
C5(Pr. 904) Terminal 4 frequency setting bias frequency
]
[
C6(Pr. 904) Terminal 4 frequency setting bias
]
[
Pr. 125 Terminal 2 frequency setting gain frequency
]
[
C4(Pr. 903) Terminal 2 frequency setting gain
]
[
Pr. 126 Terminal 4 frequency setting gain frequency
]
[
C7(Pr. 905) Terminal 4 frequency setting gain
]
1
Magnetic flux command
[
C16(Pr. 919) Terminal 1bias command (torque/magnetic flux)
]
[
C17(Pr. 919) Terminal 1bias (torque/magnetic flux)
]
[
C18(Pr. 920) Terminal 1gain command (torque/magnetic flux)
]
[
C19(Pr. 920) Terminal 1gain (torque/magnetic flux)
]
2
Regenerative torque limit
[
C16(Pr. 919) Terminal 1bias command (torque/magnetic flux)
]
[
C17(Pr. 919) Terminal 1bias (torque/magnetic flux)
]
[
C18(Pr. 920) Terminal 1gain command (torque/magnetic flux)
]
[
C19(Pr. 920) Terminal 1gain (torque/magnetic flux)
]
3
Torque command
4
Stall prevention operation
level* /Torque limit/torque
command
5
Forward/reverse rotation
speed limit
[
C12(Pr. 917) Terminal 1 bias frequency (speed)
]
[
C13(Pr. 917) Terminal 1 bias frequency (speed)
]
[
C14(Pr. 918) Terminal 1 gain frequency (speed)
]
[
C15(Pr. 918) Terminal 1 gain (speed)
]
6
Torque bias input
[
C16(Pr. 919) Terminal 1bias command (torque/magnetic flux)
]
[
C17(Pr. 919) Terminal 1bias (torque/magnetic flux)
]
[
C18(Pr. 920) Terminal 1gain command (torque/magnetic flux)
]
[
C19(Pr. 920) Terminal 1gain (torque/magnetic flux)
]
9999
—
—
—
[
Pr. 858
]
Setting
Terminal Function
Calibration Parameters
Bias setting
Gain setting
0
(initial
value)
Frequency (speed)
indication
speed limit
[
C5(Pr. 904) Terminal 4 frequency setting bias
frequency
]
[
C6(Pr. 904) Terminal 4 frequency setting bias
]
[
Pr. 126 Terminal 4 frequency setting gain frequency
]
[
C7(Pr. 905) Terminal 4 frequency setting gain
]
1
Magnetic flux command
[
C38(Pr. 932) Terminal 4 bias command (torque/
magnetic flux)
]
[
C39(Pr. 932) Terminal 4 bias (torque/magnetic flux)
]
[
C40(Pr. 933) Terminal 4 gain command (torque/
magnetic flux)
]
[
C41(Pr. 933) Terminal 4 gain (torque/magnetic flux)
]
4
Stall prevention operation
level
*
/Torque limit
[
C38(Pr. 932) Terminal 4 bias command (torque/
magnetic flux)
]
[
C39(Pr. 932) Terminal 4 bias (torque/magnetic flux)
]
[
C40(Pr. 933) Terminal 4 gain command (torque/
magnetic flux)
]
[
C41(Pr. 933) Terminal 4 gain (torque/magnetic flux)
]
9999
—
—
—
—:No function
* Use [
Pr. 148 Stall prevention level at 0V input
] and [
Pr. 149 Stall prevention level at 10V input
] to adjust bias/gain of stall prevention
operation level.
[
Pr. 406
]
Setting
Terminal Function
Calibration Parameters
Bias setting
Gain setting
0
Speed command / speed
limit
[
C30 (Pr. 926) Terminal 6 bias frequency (speed)
]
[
C31 (Pr. 926) Terminal 6 bias (speed)
]
[
C32 (Pr. 927) Terminal 6 gain frequency (speed)
]
[
C33 (Pr. 927) Terminal 6 gain (speed)
]
2
Regenerative torque limit
[
C34 (Pr. 928) Terminal 6 bias command (torque)
]
[
C35 (Pr. 928) Terminal 6 bias (torque)
]
[
C36 (Pr. 929) Terminal 6 gain command (torque)
]
[
C37 (Pr. 929) Terminal 6 gain (torque)
]
3
Torque command
4
Stall prevention operation
level* / Torque limit /
torque command
5
Forward/reverse rotation
speed limit
[
C30 (Pr. 926) Terminal 6 bias frequency (speed)
]
[
C31 (Pr. 926) Terminal 6 bias (speed)
]
[
C32 (Pr. 927) Terminal 6 gain frequency (speed)
]
[
C33 (Pr. 927) Terminal 6 gain (speed)
]
6
Torque bias input
[
C34 (Pr. 928) Terminal 6 bias command (torque)
]
[
C35 (Pr. 928) Terminal 6 bias (torque)
]
[
C36 (Pr. 929) Terminal 6 gain command (torque)
]
[
C37 (Pr. 929) Terminal 6 gain (torque)
]
9999
(initial
value)
—
—
—
—:No function
* Use [
Pr. 148 Stall prevention level at 0V input
] and [
Pr. 149 Stall prevention level at 10V input
] to adjust bias/gain of stall prevention
operation level.